14 AWG Wire — Ampacity & Voltage Drop

Complete specifications for 14 AWG conductors including ampacity ratings from NEC Table 310.16, resistance values from NEC Chapter 9 Table 8, and pre-computed voltage drop tables at multiple distances. The 14 AWG conductor has a cross-sectional area of 4,110 circular mils and a diameter of 0.0641 inches. Use the tables below for quick reference, or use the wire size calculator for custom parameters.

14 AWG Specifications

Diameter
0.0641 in
Area
4,110 CM
Cu Resistance
3.14 Ω/kft
Al Resistance
5.17 Ω/kft

Ampacity Ratings (NEC Table 310.16)

Material 60°C 75°C 90°C
Copper 15 A 20 A 25 A
Aluminum 12 A 16 A 20 A

Voltage Drop Table — 14 AWG Copper at 120V

The table below shows the voltage drop in volts and percentage for 14 AWG copper conductors at 120 volts, single-phase, at various distances and amperages. Cells highlighted in red exceed the NEC recommended 3% voltage drop limit for branch circuits. Use these values to quickly determine if 14 AWG is adequate for your 120-volt circuit at the planned distance, or if you need to upsize to a larger gauge.

Distance 15A20A30A
25 ft 2.4V
2.0%
3.1V
2.6%
4.7V
3.9%
50 ft 4.7V
3.9%
6.3V
5.2%
9.4V
7.8%
75 ft 7.1V
5.9%
9.4V
7.8%
14.1V
11.8%
100 ft 9.4V
7.8%
12.6V
10.5%
18.8V
15.7%
125 ft 11.8V
9.8%
15.7V
13.1%
23.6V
19.6%
150 ft 14.1V
11.8%
18.8V
15.7%
28.3V
23.6%
200 ft 18.8V
15.7%
25.1V
20.9%
37.7V
31.4%
250 ft 23.6V
19.6%
31.4V
26.2%
47.1V
39.3%
300 ft 28.3V
23.6%
37.7V
31.4%
56.5V
47.1%
400 ft 37.7V
31.4%
50.2V
41.9%
75.4V
62.8%
500 ft 47.1V
39.3%
62.8V
52.3%
94.2V
78.5%

Voltage Drop Table — 14 AWG Copper at 240V

The following table shows voltage drop for 14 AWG copper conductors at 240 volts, single-phase. Because 240-volt circuits have a higher supply voltage, the percentage voltage drop is lower for the same absolute voltage loss. This means 14 AWG wire can run longer distances on a 240-volt circuit before exceeding the 3% limit compared to a 120-volt circuit carrying the same current.

Distance 15A20A30A
25 ft 2.4V
1.0%
3.1V
1.3%
4.7V
2.0%
50 ft 4.7V
2.0%
6.3V
2.6%
9.4V
3.9%
75 ft 7.1V
2.9%
9.4V
3.9%
14.1V
5.9%
100 ft 9.4V
3.9%
12.6V
5.2%
18.8V
7.8%
125 ft 11.8V
4.9%
15.7V
6.5%
23.6V
9.8%
150 ft 14.1V
5.9%
18.8V
7.8%
28.3V
11.8%
200 ft 18.8V
7.8%
25.1V
10.5%
37.7V
15.7%
250 ft 23.6V
9.8%
31.4V
13.1%
47.1V
19.6%
300 ft 28.3V
11.8%
37.7V
15.7%
56.5V
23.6%
400 ft 37.7V
15.7%
50.2V
20.9%
75.4V
31.4%
500 ft 47.1V
19.6%
62.8V
26.2%
94.2V
39.3%

How Far Can You Run 14 AWG?

One of the most common questions electricians and homeowners ask is how far a particular wire gauge can run before exceeding the NEC voltage drop recommendation. The answer depends on the circuit voltage, the current draw, and whether you are using the 3% branch circuit limit or the 5% feeder-plus-branch limit. Below are maximum one-way distances for 14 AWG copper at 3% voltage drop:

Load 120V Max Distance 240V Max Distance
15 Amps 38 ft 76 ft
20 Amps 28 ft 57 ft

These distances represent the maximum one-way run from the breaker panel to the load. If your run exceeds these limits, you must use a larger wire gauge to keep the voltage drop within acceptable limits. For feeder circuits where the 5% combined limit applies, you can extend the run by approximately 67% beyond the 3% distances shown above, but only if the branch circuit portion stays within its own 3% allowance.

Common Uses for 14 AWG

14 AWG is the minimum wire size permitted by the NEC for permanent wiring in residential and commercial buildings. It is rated for 15-amp circuits at 60 degrees C and is most commonly used for general lighting circuits, bedroom receptacles, and low-draw appliance circuits. The NEC prohibits using 14 AWG for 20-amp circuits even if the load is well below 15 amps. Many electricians and local codes require 12 AWG as a minimum for all branch circuits, but 14 AWG remains code-compliant for 15-amp circuits in most jurisdictions.

When selecting 14 AWG for your installation, always verify that the ampacity meets or exceeds the circuit breaker rating, the voltage drop is within NEC recommendations for the run distance, and the terminations at both ends are rated for the conductor material and size. For circuits serving continuous loads (operating 3 hours or more), the conductor must be sized at 125% of the continuous load current. Consult NEC Article 210 for branch circuit requirements and Article 215 for feeder circuit requirements.

Other Wire Sizes

Browse specifications and voltage drop tables for other wire gauges. Selecting the correct wire size requires balancing ampacity, voltage drop, cost, and installation practicality.