12 AWG Wire — Ampacity & Voltage Drop

Complete specifications for 12 AWG conductors including ampacity ratings from NEC Table 310.16, resistance values from NEC Chapter 9 Table 8, and pre-computed voltage drop tables at multiple distances. The 12 AWG conductor has a cross-sectional area of 6,530 circular mils and a diameter of 0.0808 inches. Use the tables below for quick reference, or use the wire size calculator for custom parameters.

12 AWG Specifications

Diameter
0.0808 in
Area
6,530 CM
Cu Resistance
1.98 Ω/kft
Al Resistance
3.25 Ω/kft

Ampacity Ratings (NEC Table 310.16)

Material 60°C 75°C 90°C
Copper 20 A 25 A 30 A
Aluminum 16 A 20 A 24 A

Voltage Drop Table — 12 AWG Copper at 120V

The table below shows the voltage drop in volts and percentage for 12 AWG copper conductors at 120 volts, single-phase, at various distances and amperages. Cells highlighted in red exceed the NEC recommended 3% voltage drop limit for branch circuits. Use these values to quickly determine if 12 AWG is adequate for your 120-volt circuit at the planned distance, or if you need to upsize to a larger gauge.

Distance 15A20A30A
25 ft 1.5V
1.2%
2.0V
1.6%
3.0V
2.5%
50 ft 3.0V
2.5%
4.0V
3.3%
5.9V
5.0%
75 ft 4.5V
3.7%
5.9V
5.0%
8.9V
7.4%
100 ft 5.9V
5.0%
7.9V
6.6%
11.9V
9.9%
125 ft 7.4V
6.2%
9.9V
8.3%
14.8V
12.4%
150 ft 8.9V
7.4%
11.9V
9.9%
17.8V
14.8%
200 ft 11.9V
9.9%
15.8V
13.2%
23.8V
19.8%
250 ft 14.8V
12.4%
19.8V
16.5%
29.7V
24.8%
300 ft 17.8V
14.8%
23.8V
19.8%
35.6V
29.7%
400 ft 23.8V
19.8%
31.7V
26.4%
47.5V
39.6%
500 ft 29.7V
24.8%
39.6V
33.0%
59.4V
49.5%

Voltage Drop Table — 12 AWG Copper at 240V

The following table shows voltage drop for 12 AWG copper conductors at 240 volts, single-phase. Because 240-volt circuits have a higher supply voltage, the percentage voltage drop is lower for the same absolute voltage loss. This means 12 AWG wire can run longer distances on a 240-volt circuit before exceeding the 3% limit compared to a 120-volt circuit carrying the same current.

Distance 15A20A30A
25 ft 1.5V
0.6%
2.0V
0.8%
3.0V
1.2%
50 ft 3.0V
1.2%
4.0V
1.6%
5.9V
2.5%
75 ft 4.5V
1.9%
5.9V
2.5%
8.9V
3.7%
100 ft 5.9V
2.5%
7.9V
3.3%
11.9V
5.0%
125 ft 7.4V
3.1%
9.9V
4.1%
14.8V
6.2%
150 ft 8.9V
3.7%
11.9V
5.0%
17.8V
7.4%
200 ft 11.9V
5.0%
15.8V
6.6%
23.8V
9.9%
250 ft 14.8V
6.2%
19.8V
8.3%
29.7V
12.4%
300 ft 17.8V
7.4%
23.8V
9.9%
35.6V
14.8%
400 ft 23.8V
9.9%
31.7V
13.2%
47.5V
19.8%
500 ft 29.7V
12.4%
39.6V
16.5%
59.4V
24.8%

How Far Can You Run 12 AWG?

One of the most common questions electricians and homeowners ask is how far a particular wire gauge can run before exceeding the NEC voltage drop recommendation. The answer depends on the circuit voltage, the current draw, and whether you are using the 3% branch circuit limit or the 5% feeder-plus-branch limit. Below are maximum one-way distances for 12 AWG copper at 3% voltage drop:

Load 120V Max Distance 240V Max Distance
15 Amps 60 ft 121 ft
20 Amps 45 ft 90 ft

These distances represent the maximum one-way run from the breaker panel to the load. If your run exceeds these limits, you must use a larger wire gauge to keep the voltage drop within acceptable limits. For feeder circuits where the 5% combined limit applies, you can extend the run by approximately 67% beyond the 3% distances shown above, but only if the branch circuit portion stays within its own 3% allowance.

Common Uses for 12 AWG

12 AWG is the most widely used wire size in residential construction, rated for 20-amp circuits at 60 degrees C. It is required for kitchen countertop receptacles, bathroom receptacles, laundry circuits, and garage circuits per the NEC. Many electricians use 12 AWG exclusively for all general-purpose branch circuits because it provides more headroom than 14 AWG and allows future circuit upgrades to 20 amps without rewiring. The slightly higher cost compared to 14 AWG is negligible relative to labor costs.

When selecting 12 AWG for your installation, always verify that the ampacity meets or exceeds the circuit breaker rating, the voltage drop is within NEC recommendations for the run distance, and the terminations at both ends are rated for the conductor material and size. For circuits serving continuous loads (operating 3 hours or more), the conductor must be sized at 125% of the continuous load current. Consult NEC Article 210 for branch circuit requirements and Article 215 for feeder circuit requirements.

Other Wire Sizes

Browse specifications and voltage drop tables for other wire gauges. Selecting the correct wire size requires balancing ampacity, voltage drop, cost, and installation practicality.