120 Volt Voltage Drop Tables
120 volts is the standard household voltage in the United States for general-purpose receptacles and lighting. It is derived from a 240-volt service by using one hot conductor and the neutral. Most residential branch circuits operate at 120 volts, including bedroom outlets, kitchen countertop circuits, bathroom circuits, lighting circuits, and general-purpose receptacles throughout the home.
Understanding Voltage Drop at 120V
Voltage drop is the reduction in voltage between the source (panel) and the load (device) caused by the resistance of the conductors. At 120 volts, a 3% voltage drop equals 3.6 volts, meaning the voltage at the load would be 116.4 volts. The NEC recommends keeping voltage drop below 3% for branch circuits and below 5% for the combined feeder and branch circuit. While these are recommendations rather than mandatory requirements, they represent accepted engineering practice and are enforced by most electrical inspectors.
Branch circuits at 120V are limited to 15 or 20 amps for general lighting and receptacle loads per NEC 210.3. The 80% rule for continuous loads means a 20A circuit should carry no more than 16A continuously.
Common 120V circuits include: 15A lighting, 20A kitchen outlets, 20A bathroom GFCI, 20A laundry, 20A garage, 15A bedroom, 20A outdoor, 20A workshop, 30A RV (TT-30). Each of these applications has specific NEC requirements for wire sizing, overcurrent protection, and installation methods. The tables below provide voltage drop values for copper conductors at various distances and amperages, organized by wire gauge, so you can quickly determine whether a specific gauge is adequate for your installation.
Quick Reference: Maximum Distance by Gauge at 120V
The table below shows the maximum one-way distance for each copper wire gauge at common amperages to maintain a voltage drop of 3% or less at 120 volts (single phase). If your run distance exceeds these values, you must use a larger wire gauge.
| Gauge | 10A Max Dist | 15A Max Dist | 20A Max Dist | 30A Max Dist |
|---|---|---|---|---|
| 14 AWG | 57 ft | 38 ft | 28 ft | 19 ft |
| 12 AWG | 90 ft | 60 ft | 45 ft | 30 ft |
| 10 AWG | 145 ft | 96 ft | 72 ft | 48 ft |
| 8 AWG | 231 ft | 154 ft | 115 ft | 77 ft |
| 6 AWG | 366 ft | 244 ft | 183 ft | 122 ft |
| 4 AWG | 584 ft | 389 ft | 292 ft | 194 ft |
| 3 AWG | 734 ft | 489 ft | 367 ft | 244 ft |
| 2 AWG | 927 ft | 618 ft | 463 ft | 309 ft |
| 1 AWG | 1168 ft | 779 ft | 584 ft | 389 ft |
| 1/0 AWG | 1475 ft | 983 ft | 737 ft | 491 ft |
| 2/0 AWG | 1861 ft | 1240 ft | 930 ft | 620 ft |
| 3/0 AWG | 2349 ft | 1566 ft | 1174 ft | 783 ft |
| 4/0 AWG | 2960 ft | 1973 ft | 1480 ft | 986 ft |
| 250 kcmil | 3495 ft | 2330 ft | 1747 ft | 1165 ft |
| 300 kcmil | 4195 ft | 2797 ft | 2097 ft | 1398 ft |
| 350 kcmil | 4904 ft | 3269 ft | 2452 ft | 1634 ft |
| 400 kcmil | 5607 ft | 3738 ft | 2803 ft | 1869 ft |
| 500 kcmil | 6976 ft | 4651 ft | 3488 ft | 2325 ft |
14 AWG Voltage Drop at 120V
Voltage drop values for 14 AWG copper conductor (3.14 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 20A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 1.6V 1.3% | 2.4V 2.0% | 3.1V 2.6% | 4.7V 3.9% |
| 50 ft | 3.1V 2.6% | 4.7V 3.9% | 6.3V 5.2% | 9.4V 7.8% |
| 75 ft | 4.7V 3.9% | 7.1V 5.9% | 9.4V 7.8% | 14.1V 11.8% |
| 100 ft | 6.3V 5.2% | 9.4V 7.8% | 12.6V 10.5% | 18.8V 15.7% |
| 125 ft | 7.8V 6.5% | 11.8V 9.8% | 15.7V 13.1% | 23.6V 19.6% |
| 150 ft | 9.4V 7.8% | 14.1V 11.8% | 18.8V 15.7% | 28.3V 23.6% |
| 200 ft | 12.6V 10.5% | 18.8V 15.7% | 25.1V 20.9% | 37.7V 31.4% |
| 250 ft | 15.7V 13.1% | 23.6V 19.6% | 31.4V 26.2% | 47.1V 39.3% |
| 300 ft | 18.8V 15.7% | 28.3V 23.6% | 37.7V 31.4% | 56.5V 47.1% |
| 400 ft | 25.1V 20.9% | 37.7V 31.4% | 50.2V 41.9% | 75.4V 62.8% |
| 500 ft | 31.4V 26.2% | 47.1V 39.3% | 62.8V 52.3% | 94.2V 78.5% |
12 AWG Voltage Drop at 120V
Voltage drop values for 12 AWG copper conductor (1.98 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 25A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 1.0V 0.8% | 1.5V 1.2% | 2.0V 1.6% | 3.0V 2.5% |
| 50 ft | 2.0V 1.6% | 3.0V 2.5% | 4.0V 3.3% | 5.9V 5.0% |
| 75 ft | 3.0V 2.5% | 4.5V 3.7% | 5.9V 5.0% | 8.9V 7.4% |
| 100 ft | 4.0V 3.3% | 5.9V 5.0% | 7.9V 6.6% | 11.9V 9.9% |
| 125 ft | 5.0V 4.1% | 7.4V 6.2% | 9.9V 8.3% | 14.8V 12.4% |
| 150 ft | 5.9V 5.0% | 8.9V 7.4% | 11.9V 9.9% | 17.8V 14.8% |
| 200 ft | 7.9V 6.6% | 11.9V 9.9% | 15.8V 13.2% | 23.8V 19.8% |
| 250 ft | 9.9V 8.3% | 14.8V 12.4% | 19.8V 16.5% | 29.7V 24.8% |
| 300 ft | 11.9V 9.9% | 17.8V 14.8% | 23.8V 19.8% | 35.6V 29.7% |
| 400 ft | 15.8V 13.2% | 23.8V 19.8% | 31.7V 26.4% | 47.5V 39.6% |
| 500 ft | 19.8V 16.5% | 29.7V 24.8% | 39.6V 33.0% | 59.4V 49.5% |
10 AWG Voltage Drop at 120V
Voltage drop values for 10 AWG copper conductor (1.24 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 35A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.6V 0.5% | 0.9V 0.8% | 1.2V 1.0% | 1.9V 1.6% |
| 50 ft | 1.2V 1.0% | 1.9V 1.6% | 2.5V 2.1% | 3.7V 3.1% |
| 75 ft | 1.9V 1.6% | 2.8V 2.3% | 3.7V 3.1% | 5.6V 4.7% |
| 100 ft | 2.5V 2.1% | 3.7V 3.1% | 5.0V 4.1% | 7.4V 6.2% |
| 125 ft | 3.1V 2.6% | 4.7V 3.9% | 6.2V 5.2% | 9.3V 7.8% |
| 150 ft | 3.7V 3.1% | 5.6V 4.7% | 7.4V 6.2% | 11.2V 9.3% |
| 200 ft | 5.0V 4.1% | 7.4V 6.2% | 9.9V 8.3% | 14.9V 12.4% |
| 250 ft | 6.2V 5.2% | 9.3V 7.8% | 12.4V 10.3% | 18.6V 15.5% |
| 300 ft | 7.4V 6.2% | 11.2V 9.3% | 14.9V 12.4% | 22.3V 18.6% |
| 400 ft | 9.9V 8.3% | 14.9V 12.4% | 19.8V 16.5% | 29.8V 24.8% |
| 500 ft | 12.4V 10.3% | 18.6V 15.5% | 24.8V 20.7% | 37.2V 31.0% |
8 AWG Voltage Drop at 120V
Voltage drop values for 8 AWG copper conductor (0.778 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 50A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.4V 0.3% | 0.6V 0.5% | 0.8V 0.7% | 1.2V 1.0% |
| 50 ft | 0.8V 0.7% | 1.2V 1.0% | 1.6V 1.3% | 2.3V 1.9% |
| 75 ft | 1.2V 1.0% | 1.8V 1.5% | 2.3V 1.9% | 3.5V 2.9% |
| 100 ft | 1.6V 1.3% | 2.3V 1.9% | 3.1V 2.6% | 4.7V 3.9% |
| 125 ft | 1.9V 1.6% | 2.9V 2.4% | 3.9V 3.2% | 5.8V 4.9% |
| 150 ft | 2.3V 1.9% | 3.5V 2.9% | 4.7V 3.9% | 7.0V 5.8% |
| 200 ft | 3.1V 2.6% | 4.7V 3.9% | 6.2V 5.2% | 9.3V 7.8% |
| 250 ft | 3.9V 3.2% | 5.8V 4.9% | 7.8V 6.5% | 11.7V 9.7% |
| 300 ft | 4.7V 3.9% | 7.0V 5.8% | 9.3V 7.8% | 14.0V 11.7% |
| 400 ft | 6.2V 5.2% | 9.3V 7.8% | 12.4V 10.4% | 18.7V 15.6% |
| 500 ft | 7.8V 6.5% | 11.7V 9.7% | 15.6V 13.0% | 23.3V 19.4% |
6 AWG Voltage Drop at 120V
Voltage drop values for 6 AWG copper conductor (0.491 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 65A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.3V 0.2% | 0.4V 0.3% | 0.5V 0.4% | 0.7V 0.6% |
| 50 ft | 0.5V 0.4% | 0.7V 0.6% | 1.0V 0.8% | 1.5V 1.2% |
| 75 ft | 0.7V 0.6% | 1.1V 0.9% | 1.5V 1.2% | 2.2V 1.8% |
| 100 ft | 1.0V 0.8% | 1.5V 1.2% | 2.0V 1.6% | 3.0V 2.5% |
| 125 ft | 1.2V 1.0% | 1.8V 1.5% | 2.5V 2.0% | 3.7V 3.1% |
| 150 ft | 1.5V 1.2% | 2.2V 1.8% | 3.0V 2.5% | 4.4V 3.7% |
| 200 ft | 2.0V 1.6% | 3.0V 2.5% | 3.9V 3.3% | 5.9V 4.9% |
| 250 ft | 2.5V 2.0% | 3.7V 3.1% | 4.9V 4.1% | 7.4V 6.1% |
| 300 ft | 3.0V 2.5% | 4.4V 3.7% | 5.9V 4.9% | 8.8V 7.4% |
| 400 ft | 3.9V 3.3% | 5.9V 4.9% | 7.9V 6.5% | 11.8V 9.8% |
| 500 ft | 4.9V 4.1% | 7.4V 6.1% | 9.8V 8.2% | 14.7V 12.3% |
4 AWG Voltage Drop at 120V
Voltage drop values for 4 AWG copper conductor (0.308 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 85A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.1V 0.1% | 0.2V 0.2% | 0.3V 0.3% | 0.5V 0.4% |
| 50 ft | 0.3V 0.3% | 0.5V 0.4% | 0.6V 0.5% | 0.9V 0.8% |
| 75 ft | 0.5V 0.4% | 0.7V 0.6% | 0.9V 0.8% | 1.4V 1.2% |
| 100 ft | 0.6V 0.5% | 0.9V 0.8% | 1.2V 1.0% | 1.9V 1.5% |
| 125 ft | 0.8V 0.6% | 1.2V 1.0% | 1.5V 1.3% | 2.3V 1.9% |
| 150 ft | 0.9V 0.8% | 1.4V 1.2% | 1.9V 1.5% | 2.8V 2.3% |
| 200 ft | 1.2V 1.0% | 1.9V 1.5% | 2.5V 2.0% | 3.7V 3.1% |
| 250 ft | 1.5V 1.3% | 2.3V 1.9% | 3.1V 2.6% | 4.6V 3.9% |
| 300 ft | 1.9V 1.5% | 2.8V 2.3% | 3.7V 3.1% | 5.5V 4.6% |
| 400 ft | 2.5V 2.0% | 3.7V 3.1% | 4.9V 4.1% | 7.4V 6.2% |
| 500 ft | 3.1V 2.6% | 4.6V 3.9% | 6.2V 5.1% | 9.2V 7.7% |
3 AWG Voltage Drop at 120V
Voltage drop values for 3 AWG copper conductor (0.245 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 100A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.1V 0.1% | 0.2V 0.1% | 0.3V 0.2% | 0.4V 0.3% |
| 50 ft | 0.3V 0.2% | 0.4V 0.3% | 0.5V 0.4% | 0.7V 0.6% |
| 75 ft | 0.4V 0.3% | 0.6V 0.5% | 0.7V 0.6% | 1.1V 0.9% |
| 100 ft | 0.5V 0.4% | 0.7V 0.6% | 1.0V 0.8% | 1.5V 1.2% |
| 125 ft | 0.6V 0.5% | 0.9V 0.8% | 1.2V 1.0% | 1.8V 1.5% |
| 150 ft | 0.7V 0.6% | 1.1V 0.9% | 1.5V 1.2% | 2.2V 1.8% |
| 200 ft | 1.0V 0.8% | 1.5V 1.2% | 2.0V 1.6% | 2.9V 2.5% |
| 250 ft | 1.2V 1.0% | 1.8V 1.5% | 2.5V 2.0% | 3.7V 3.1% |
| 300 ft | 1.5V 1.2% | 2.2V 1.8% | 2.9V 2.5% | 4.4V 3.7% |
| 400 ft | 2.0V 1.6% | 2.9V 2.5% | 3.9V 3.3% | 5.9V 4.9% |
| 500 ft | 2.5V 2.0% | 3.7V 3.1% | 4.9V 4.1% | 7.3V 6.1% |
2 AWG Voltage Drop at 120V
Voltage drop values for 2 AWG copper conductor (0.194 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 115A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.2% | 0.3V 0.2% |
| 50 ft | 0.2V 0.2% | 0.3V 0.2% | 0.4V 0.3% | 0.6V 0.5% |
| 75 ft | 0.3V 0.2% | 0.4V 0.4% | 0.6V 0.5% | 0.9V 0.7% |
| 100 ft | 0.4V 0.3% | 0.6V 0.5% | 0.8V 0.7% | 1.2V 1.0% |
| 125 ft | 0.5V 0.4% | 0.7V 0.6% | 1.0V 0.8% | 1.5V 1.2% |
| 150 ft | 0.6V 0.5% | 0.9V 0.7% | 1.2V 1.0% | 1.8V 1.5% |
| 200 ft | 0.8V 0.7% | 1.2V 1.0% | 1.6V 1.3% | 2.3V 1.9% |
| 250 ft | 1.0V 0.8% | 1.5V 1.2% | 1.9V 1.6% | 2.9V 2.4% |
| 300 ft | 1.2V 1.0% | 1.8V 1.5% | 2.3V 1.9% | 3.5V 2.9% |
| 400 ft | 1.6V 1.3% | 2.3V 1.9% | 3.1V 2.6% | 4.7V 3.9% |
| 500 ft | 1.9V 1.6% | 2.9V 2.4% | 3.9V 3.2% | 5.8V 4.8% |
1 AWG Voltage Drop at 120V
Voltage drop values for 1 AWG copper conductor (0.154 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 130A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.1V 0.1% | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.2% |
| 50 ft | 0.1V 0.1% | 0.2V 0.2% | 0.3V 0.3% | 0.5V 0.4% |
| 75 ft | 0.2V 0.2% | 0.3V 0.3% | 0.5V 0.4% | 0.7V 0.6% |
| 100 ft | 0.3V 0.3% | 0.5V 0.4% | 0.6V 0.5% | 0.9V 0.8% |
| 125 ft | 0.4V 0.3% | 0.6V 0.5% | 0.8V 0.6% | 1.2V 1.0% |
| 150 ft | 0.5V 0.4% | 0.7V 0.6% | 0.9V 0.8% | 1.4V 1.2% |
| 200 ft | 0.6V 0.5% | 0.9V 0.8% | 1.2V 1.0% | 1.9V 1.5% |
| 250 ft | 0.8V 0.6% | 1.2V 1.0% | 1.5V 1.3% | 2.3V 1.9% |
| 300 ft | 0.9V 0.8% | 1.4V 1.2% | 1.9V 1.5% | 2.8V 2.3% |
| 400 ft | 1.2V 1.0% | 1.9V 1.5% | 2.5V 2.0% | 3.7V 3.1% |
| 500 ft | 1.5V 1.3% | 2.3V 1.9% | 3.1V 2.6% | 4.6V 3.9% |
1/0 AWG Voltage Drop at 120V
Voltage drop values for 1/0 AWG copper conductor (0.122 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 150A. Cells in red exceed the 3% NEC recommendation.
| Distance | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| 25 ft | 0.1V 0.1% | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.1% |
| 50 ft | 0.1V 0.1% | 0.2V 0.1% | 0.2V 0.2% | 0.4V 0.3% |
| 75 ft | 0.2V 0.1% | 0.3V 0.2% | 0.4V 0.3% | 0.6V 0.5% |
| 100 ft | 0.2V 0.2% | 0.4V 0.3% | 0.5V 0.4% | 0.7V 0.6% |
| 125 ft | 0.3V 0.3% | 0.5V 0.4% | 0.6V 0.5% | 0.9V 0.8% |
| 150 ft | 0.4V 0.3% | 0.6V 0.5% | 0.7V 0.6% | 1.1V 0.9% |
| 200 ft | 0.5V 0.4% | 0.7V 0.6% | 1.0V 0.8% | 1.5V 1.2% |
| 250 ft | 0.6V 0.5% | 0.9V 0.8% | 1.2V 1.0% | 1.8V 1.5% |
| 300 ft | 0.7V 0.6% | 1.1V 0.9% | 1.5V 1.2% | 2.2V 1.8% |
| 400 ft | 1.0V 0.8% | 1.5V 1.2% | 1.9V 1.6% | 2.9V 2.4% |
| 500 ft | 1.2V 1.0% | 1.8V 1.5% | 2.4V 2.0% | 3.7V 3.0% |
Other Voltage Levels
View voltage drop tables for other standard voltages. Higher voltages result in lower percentage voltage drop for the same absolute voltage loss, which allows longer conductor runs without upsizing.
Tools and Training for Electricians
Quality resources for your next wiring project.
Some links above are affiliate links — if you buy through them we may earn a small commission at no extra cost to you. As an Amazon Associate we earn from qualifying purchases.