Skip to content

120 Volt Voltage Drop Tables

120 volts is the standard household voltage in the United States for general-purpose receptacles and lighting. It is derived from a 240-volt service by using one hot conductor and the neutral. Most residential branch circuits operate at 120 volts, including bedroom outlets, kitchen countertop circuits, bathroom circuits, lighting circuits, and general-purpose receptacles throughout the home.

Understanding Voltage Drop at 120V

Voltage drop is the reduction in voltage between the source (panel) and the load (device) caused by the resistance of the conductors. At 120 volts, a 3% voltage drop equals 3.6 volts, meaning the voltage at the load would be 116.4 volts. The NEC recommends keeping voltage drop below 3% for branch circuits and below 5% for the combined feeder and branch circuit. While these are recommendations rather than mandatory requirements, they represent accepted engineering practice and are enforced by most electrical inspectors.

Branch circuits at 120V are limited to 15 or 20 amps for general lighting and receptacle loads per NEC 210.3. The 80% rule for continuous loads means a 20A circuit should carry no more than 16A continuously.

Common 120V circuits include: 15A lighting, 20A kitchen outlets, 20A bathroom GFCI, 20A laundry, 20A garage, 15A bedroom, 20A outdoor, 20A workshop, 30A RV (TT-30). Each of these applications has specific NEC requirements for wire sizing, overcurrent protection, and installation methods. The tables below provide voltage drop values for copper conductors at various distances and amperages, organized by wire gauge, so you can quickly determine whether a specific gauge is adequate for your installation.

Quick Reference: Maximum Distance by Gauge at 120V

The table below shows the maximum one-way distance for each copper wire gauge at common amperages to maintain a voltage drop of 3% or less at 120 volts (single phase). If your run distance exceeds these values, you must use a larger wire gauge.

Gauge 10A Max Dist15A Max Dist20A Max Dist30A Max Dist
14 AWG 57 ft38 ft28 ft19 ft
12 AWG 90 ft60 ft45 ft30 ft
10 AWG 145 ft96 ft72 ft48 ft
8 AWG 231 ft154 ft115 ft77 ft
6 AWG 366 ft244 ft183 ft122 ft
4 AWG 584 ft389 ft292 ft194 ft
3 AWG 734 ft489 ft367 ft244 ft
2 AWG 927 ft618 ft463 ft309 ft
1 AWG 1168 ft779 ft584 ft389 ft
1/0 AWG 1475 ft983 ft737 ft491 ft
2/0 AWG 1861 ft1240 ft930 ft620 ft
3/0 AWG 2349 ft1566 ft1174 ft783 ft
4/0 AWG 2960 ft1973 ft1480 ft986 ft
250 kcmil 3495 ft2330 ft1747 ft1165 ft
300 kcmil 4195 ft2797 ft2097 ft1398 ft
350 kcmil 4904 ft3269 ft2452 ft1634 ft
400 kcmil 5607 ft3738 ft2803 ft1869 ft
500 kcmil 6976 ft4651 ft3488 ft2325 ft

14 AWG Voltage Drop at 120V

Voltage drop values for 14 AWG copper conductor (3.14 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 20A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 1.6V
1.3%
2.4V
2.0%
3.1V
2.6%
4.7V
3.9%
50 ft 3.1V
2.6%
4.7V
3.9%
6.3V
5.2%
9.4V
7.8%
75 ft 4.7V
3.9%
7.1V
5.9%
9.4V
7.8%
14.1V
11.8%
100 ft 6.3V
5.2%
9.4V
7.8%
12.6V
10.5%
18.8V
15.7%
125 ft 7.8V
6.5%
11.8V
9.8%
15.7V
13.1%
23.6V
19.6%
150 ft 9.4V
7.8%
14.1V
11.8%
18.8V
15.7%
28.3V
23.6%
200 ft 12.6V
10.5%
18.8V
15.7%
25.1V
20.9%
37.7V
31.4%
250 ft 15.7V
13.1%
23.6V
19.6%
31.4V
26.2%
47.1V
39.3%
300 ft 18.8V
15.7%
28.3V
23.6%
37.7V
31.4%
56.5V
47.1%
400 ft 25.1V
20.9%
37.7V
31.4%
50.2V
41.9%
75.4V
62.8%
500 ft 31.4V
26.2%
47.1V
39.3%
62.8V
52.3%
94.2V
78.5%

12 AWG Voltage Drop at 120V

Voltage drop values for 12 AWG copper conductor (1.98 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 25A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 1.0V
0.8%
1.5V
1.2%
2.0V
1.6%
3.0V
2.5%
50 ft 2.0V
1.6%
3.0V
2.5%
4.0V
3.3%
5.9V
5.0%
75 ft 3.0V
2.5%
4.5V
3.7%
5.9V
5.0%
8.9V
7.4%
100 ft 4.0V
3.3%
5.9V
5.0%
7.9V
6.6%
11.9V
9.9%
125 ft 5.0V
4.1%
7.4V
6.2%
9.9V
8.3%
14.8V
12.4%
150 ft 5.9V
5.0%
8.9V
7.4%
11.9V
9.9%
17.8V
14.8%
200 ft 7.9V
6.6%
11.9V
9.9%
15.8V
13.2%
23.8V
19.8%
250 ft 9.9V
8.3%
14.8V
12.4%
19.8V
16.5%
29.7V
24.8%
300 ft 11.9V
9.9%
17.8V
14.8%
23.8V
19.8%
35.6V
29.7%
400 ft 15.8V
13.2%
23.8V
19.8%
31.7V
26.4%
47.5V
39.6%
500 ft 19.8V
16.5%
29.7V
24.8%
39.6V
33.0%
59.4V
49.5%

10 AWG Voltage Drop at 120V

Voltage drop values for 10 AWG copper conductor (1.24 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 35A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.6V
0.5%
0.9V
0.8%
1.2V
1.0%
1.9V
1.6%
50 ft 1.2V
1.0%
1.9V
1.6%
2.5V
2.1%
3.7V
3.1%
75 ft 1.9V
1.6%
2.8V
2.3%
3.7V
3.1%
5.6V
4.7%
100 ft 2.5V
2.1%
3.7V
3.1%
5.0V
4.1%
7.4V
6.2%
125 ft 3.1V
2.6%
4.7V
3.9%
6.2V
5.2%
9.3V
7.8%
150 ft 3.7V
3.1%
5.6V
4.7%
7.4V
6.2%
11.2V
9.3%
200 ft 5.0V
4.1%
7.4V
6.2%
9.9V
8.3%
14.9V
12.4%
250 ft 6.2V
5.2%
9.3V
7.8%
12.4V
10.3%
18.6V
15.5%
300 ft 7.4V
6.2%
11.2V
9.3%
14.9V
12.4%
22.3V
18.6%
400 ft 9.9V
8.3%
14.9V
12.4%
19.8V
16.5%
29.8V
24.8%
500 ft 12.4V
10.3%
18.6V
15.5%
24.8V
20.7%
37.2V
31.0%

8 AWG Voltage Drop at 120V

Voltage drop values for 8 AWG copper conductor (0.778 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 50A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.4V
0.3%
0.6V
0.5%
0.8V
0.7%
1.2V
1.0%
50 ft 0.8V
0.7%
1.2V
1.0%
1.6V
1.3%
2.3V
1.9%
75 ft 1.2V
1.0%
1.8V
1.5%
2.3V
1.9%
3.5V
2.9%
100 ft 1.6V
1.3%
2.3V
1.9%
3.1V
2.6%
4.7V
3.9%
125 ft 1.9V
1.6%
2.9V
2.4%
3.9V
3.2%
5.8V
4.9%
150 ft 2.3V
1.9%
3.5V
2.9%
4.7V
3.9%
7.0V
5.8%
200 ft 3.1V
2.6%
4.7V
3.9%
6.2V
5.2%
9.3V
7.8%
250 ft 3.9V
3.2%
5.8V
4.9%
7.8V
6.5%
11.7V
9.7%
300 ft 4.7V
3.9%
7.0V
5.8%
9.3V
7.8%
14.0V
11.7%
400 ft 6.2V
5.2%
9.3V
7.8%
12.4V
10.4%
18.7V
15.6%
500 ft 7.8V
6.5%
11.7V
9.7%
15.6V
13.0%
23.3V
19.4%

6 AWG Voltage Drop at 120V

Voltage drop values for 6 AWG copper conductor (0.491 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 65A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.3V
0.2%
0.4V
0.3%
0.5V
0.4%
0.7V
0.6%
50 ft 0.5V
0.4%
0.7V
0.6%
1.0V
0.8%
1.5V
1.2%
75 ft 0.7V
0.6%
1.1V
0.9%
1.5V
1.2%
2.2V
1.8%
100 ft 1.0V
0.8%
1.5V
1.2%
2.0V
1.6%
3.0V
2.5%
125 ft 1.2V
1.0%
1.8V
1.5%
2.5V
2.0%
3.7V
3.1%
150 ft 1.5V
1.2%
2.2V
1.8%
3.0V
2.5%
4.4V
3.7%
200 ft 2.0V
1.6%
3.0V
2.5%
3.9V
3.3%
5.9V
4.9%
250 ft 2.5V
2.0%
3.7V
3.1%
4.9V
4.1%
7.4V
6.1%
300 ft 3.0V
2.5%
4.4V
3.7%
5.9V
4.9%
8.8V
7.4%
400 ft 3.9V
3.3%
5.9V
4.9%
7.9V
6.5%
11.8V
9.8%
500 ft 4.9V
4.1%
7.4V
6.1%
9.8V
8.2%
14.7V
12.3%

4 AWG Voltage Drop at 120V

Voltage drop values for 4 AWG copper conductor (0.308 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 85A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.1V
0.1%
0.2V
0.2%
0.3V
0.3%
0.5V
0.4%
50 ft 0.3V
0.3%
0.5V
0.4%
0.6V
0.5%
0.9V
0.8%
75 ft 0.5V
0.4%
0.7V
0.6%
0.9V
0.8%
1.4V
1.2%
100 ft 0.6V
0.5%
0.9V
0.8%
1.2V
1.0%
1.9V
1.5%
125 ft 0.8V
0.6%
1.2V
1.0%
1.5V
1.3%
2.3V
1.9%
150 ft 0.9V
0.8%
1.4V
1.2%
1.9V
1.5%
2.8V
2.3%
200 ft 1.2V
1.0%
1.9V
1.5%
2.5V
2.0%
3.7V
3.1%
250 ft 1.5V
1.3%
2.3V
1.9%
3.1V
2.6%
4.6V
3.9%
300 ft 1.9V
1.5%
2.8V
2.3%
3.7V
3.1%
5.5V
4.6%
400 ft 2.5V
2.0%
3.7V
3.1%
4.9V
4.1%
7.4V
6.2%
500 ft 3.1V
2.6%
4.6V
3.9%
6.2V
5.1%
9.2V
7.7%

3 AWG Voltage Drop at 120V

Voltage drop values for 3 AWG copper conductor (0.245 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 100A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.1V
0.1%
0.2V
0.1%
0.3V
0.2%
0.4V
0.3%
50 ft 0.3V
0.2%
0.4V
0.3%
0.5V
0.4%
0.7V
0.6%
75 ft 0.4V
0.3%
0.6V
0.5%
0.7V
0.6%
1.1V
0.9%
100 ft 0.5V
0.4%
0.7V
0.6%
1.0V
0.8%
1.5V
1.2%
125 ft 0.6V
0.5%
0.9V
0.8%
1.2V
1.0%
1.8V
1.5%
150 ft 0.7V
0.6%
1.1V
0.9%
1.5V
1.2%
2.2V
1.8%
200 ft 1.0V
0.8%
1.5V
1.2%
2.0V
1.6%
2.9V
2.5%
250 ft 1.2V
1.0%
1.8V
1.5%
2.5V
2.0%
3.7V
3.1%
300 ft 1.5V
1.2%
2.2V
1.8%
2.9V
2.5%
4.4V
3.7%
400 ft 2.0V
1.6%
2.9V
2.5%
3.9V
3.3%
5.9V
4.9%
500 ft 2.5V
2.0%
3.7V
3.1%
4.9V
4.1%
7.3V
6.1%

2 AWG Voltage Drop at 120V

Voltage drop values for 2 AWG copper conductor (0.194 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 115A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.1V
0.1%
0.1V
0.1%
0.2V
0.2%
0.3V
0.2%
50 ft 0.2V
0.2%
0.3V
0.2%
0.4V
0.3%
0.6V
0.5%
75 ft 0.3V
0.2%
0.4V
0.4%
0.6V
0.5%
0.9V
0.7%
100 ft 0.4V
0.3%
0.6V
0.5%
0.8V
0.7%
1.2V
1.0%
125 ft 0.5V
0.4%
0.7V
0.6%
1.0V
0.8%
1.5V
1.2%
150 ft 0.6V
0.5%
0.9V
0.7%
1.2V
1.0%
1.8V
1.5%
200 ft 0.8V
0.7%
1.2V
1.0%
1.6V
1.3%
2.3V
1.9%
250 ft 1.0V
0.8%
1.5V
1.2%
1.9V
1.6%
2.9V
2.4%
300 ft 1.2V
1.0%
1.8V
1.5%
2.3V
1.9%
3.5V
2.9%
400 ft 1.6V
1.3%
2.3V
1.9%
3.1V
2.6%
4.7V
3.9%
500 ft 1.9V
1.6%
2.9V
2.4%
3.9V
3.2%
5.8V
4.8%

1 AWG Voltage Drop at 120V

Voltage drop values for 1 AWG copper conductor (0.154 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 130A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.1V
0.1%
0.1V
0.1%
0.1V
0.1%
0.2V
0.2%
50 ft 0.1V
0.1%
0.2V
0.2%
0.3V
0.3%
0.5V
0.4%
75 ft 0.2V
0.2%
0.3V
0.3%
0.5V
0.4%
0.7V
0.6%
100 ft 0.3V
0.3%
0.5V
0.4%
0.6V
0.5%
0.9V
0.8%
125 ft 0.4V
0.3%
0.6V
0.5%
0.8V
0.6%
1.2V
1.0%
150 ft 0.5V
0.4%
0.7V
0.6%
0.9V
0.8%
1.4V
1.2%
200 ft 0.6V
0.5%
0.9V
0.8%
1.2V
1.0%
1.9V
1.5%
250 ft 0.8V
0.6%
1.2V
1.0%
1.5V
1.3%
2.3V
1.9%
300 ft 0.9V
0.8%
1.4V
1.2%
1.9V
1.5%
2.8V
2.3%
400 ft 1.2V
1.0%
1.9V
1.5%
2.5V
2.0%
3.7V
3.1%
500 ft 1.5V
1.3%
2.3V
1.9%
3.1V
2.6%
4.6V
3.9%

1/0 AWG Voltage Drop at 120V

Voltage drop values for 1/0 AWG copper conductor (0.122 ohms/kft) at 120 volts, single phase. Ampacity at 75°C: 150A. Cells in red exceed the 3% NEC recommendation.

Distance 10A15A20A30A
25 ft 0.1V
0.1%
0.1V
0.1%
0.1V
0.1%
0.2V
0.1%
50 ft 0.1V
0.1%
0.2V
0.1%
0.2V
0.2%
0.4V
0.3%
75 ft 0.2V
0.1%
0.3V
0.2%
0.4V
0.3%
0.6V
0.5%
100 ft 0.2V
0.2%
0.4V
0.3%
0.5V
0.4%
0.7V
0.6%
125 ft 0.3V
0.3%
0.5V
0.4%
0.6V
0.5%
0.9V
0.8%
150 ft 0.4V
0.3%
0.6V
0.5%
0.7V
0.6%
1.1V
0.9%
200 ft 0.5V
0.4%
0.7V
0.6%
1.0V
0.8%
1.5V
1.2%
250 ft 0.6V
0.5%
0.9V
0.8%
1.2V
1.0%
1.8V
1.5%
300 ft 0.7V
0.6%
1.1V
0.9%
1.5V
1.2%
2.2V
1.8%
400 ft 1.0V
0.8%
1.5V
1.2%
1.9V
1.6%
2.9V
2.4%
500 ft 1.2V
1.0%
1.8V
1.5%
2.4V
2.0%
3.7V
3.0%

Other Voltage Levels

View voltage drop tables for other standard voltages. Higher voltages result in lower percentage voltage drop for the same absolute voltage loss, which allows longer conductor runs without upsizing.

Tools and Training for Electricians

Quality resources for your next wiring project.

Some links above are affiliate links — if you buy through them we may earn a small commission at no extra cost to you. As an Amazon Associate we earn from qualifying purchases.