200A Service Entrance — Wire Size Guide

200-amp service entrance conductors from the utility meter to the main panel. These conductors must be sized to handle the full calculated load of the dwelling. For copper, 2/0 AWG is typically required; for aluminum, 4/0 AWG is standard. The service entrance equipment must be rated for the available fault current.

Voltage
240V
Amperage
200A
Phase
Single-Phase
NEC Reference
NEC 230.42, 230.79(C), 230.90

Copper Wire Size by Distance

The table below shows the recommended copper wire gauge for a 200A Service Entrance circuit (240V, 200A, Single-Phase) at various one-way distances from the panel. Two voltage drop limits are shown: 3% for branch circuits and 5% for feeder-plus-branch combined. The ampacity column is based on NEC Table 310.16 at 75 degrees C. When the 3% and 5% columns show different gauges, the distance is long enough that voltage drop — not ampacity — is the controlling factor, and you must use the gauge appropriate for your circuit type.

Distance 3% Drop Gauge 3% Drop (V) 3% Drop (%) 5% Drop Gauge 5% Drop (V) 5% Drop (%)
25 ft 3/0 AWG 0.77 0.32% 3/0 AWG 0.77 0.32%
50 ft 3/0 AWG 1.53 0.64% 3/0 AWG 1.53 0.64%
75 ft 3/0 AWG 2.30 0.96% 3/0 AWG 2.30 0.96%
100 ft 3/0 AWG 3.06 1.28% 3/0 AWG 3.06 1.28%
125 ft 3/0 AWG 3.83 1.60% 3/0 AWG 3.83 1.60%
150 ft 3/0 AWG 4.60 1.92% 3/0 AWG 4.60 1.92%
200 ft 3/0 AWG 6.13 2.55% 3/0 AWG 6.13 2.55%
250 ft 4/0 AWG 6.08 2.53% 3/0 AWG 7.66 3.19%
300 ft 250 kcmil 6.18 2.58% 3/0 AWG 9.19 3.83%
400 ft 300 kcmil 6.86 2.86% 4/0 AWG 9.73 4.05%
500 ft 400 kcmil 6.42 2.68% 250 kcmil 10.30 4.29%

Aluminum Wire Size by Distance

Aluminum conductors cost less and weigh less than copper but have higher resistance, requiring larger gauge sizes to carry the same current. The table below shows the recommended aluminum wire gauge for this 200A Service Entrance circuit at various distances. Aluminum is a practical choice for longer feeder runs and service entrance conductors where the material savings justify the larger conductor size. All aluminum terminations must be rated for aluminum use (AL-CU marking) and treated with anti-oxidant compound.

Distance 3% Drop Gauge 3% Drop (V) 3% Drop (%) 5% Drop Gauge 5% Drop (V) 5% Drop (%)
25 ft 250 kcmil 0.85 0.35% 250 kcmil 0.85 0.35%
50 ft 250 kcmil 1.69 0.71% 250 kcmil 1.69 0.71%
75 ft 250 kcmil 2.54 1.06% 250 kcmil 2.54 1.06%
100 ft 250 kcmil 3.39 1.41% 250 kcmil 3.39 1.41%
125 ft 250 kcmil 4.24 1.76% 250 kcmil 4.24 1.76%
150 ft 250 kcmil 5.08 2.12% 250 kcmil 5.08 2.12%
200 ft 250 kcmil 6.78 2.82% 250 kcmil 6.78 2.82%
250 ft 300 kcmil 7.07 2.95% 250 kcmil 8.47 3.53%
300 ft 400 kcmil 6.35 2.64% 250 kcmil 10.16 4.23%
400 ft 500 kcmil 6.78 2.83% 300 kcmil 11.31 4.71%
500 ft N/A - - 400 kcmil 10.58 4.41%

Installation Tips for 200A Service Entrance

Proper installation is just as important as selecting the correct wire size. The following tips address the key NEC requirements and best practices specific to 200a service entrance circuits. Always verify these requirements against the current edition of the NEC and your local code amendments before beginning work.

  • This is a 240-volt circuit requiring two hot conductors, a neutral (if needed), and an equipment grounding conductor. Use a two-pole breaker rated for the circuit amperage.
  • Service entrance conductors must be sized per NEC 230.42 based on the calculated load. The main breaker must not exceed the service conductor ampacity.
  • The service entrance must include a main disconnect within sight of the meter location. All service equipment must be rated for the available fault current from the utility.
  • All outdoor receptacles must have GFCI protection and weatherproof covers. Use in-use (while-in-use) covers if cord-and-plug-connected equipment may be left plugged in.
  • All wire connections must be made with listed connectors and torqued to manufacturer specifications. Use anti-oxidant compound on all aluminum connections.
  • Verify local code amendments, as your jurisdiction may have requirements beyond the NEC minimum. Always pull a permit and schedule inspections for electrical work.

NEC Code References

The 200A Service Entrance circuit is governed by NEC 230.42, 230.79(C), 230.90. These NEC sections specify the minimum requirements for circuit sizing, overcurrent protection, grounding, and installation methods. The wire sizing in this guide is based on the following NEC tables and articles:

  • NEC Table 310.16 — Ampacity of insulated conductors rated 0-2000V in raceways, cables, or direct buried. Provides the maximum current each gauge can safely carry at 60, 75, and 90 degrees C.
  • NEC Chapter 9, Table 8 — Conductor properties including DC resistance per 1000 feet for uncoated copper and aluminum. These resistance values are used in the voltage drop formula.
  • NEC 210.19(A) Informational Note No. 4 — Recommends that branch circuit conductors be sized so that the voltage drop does not exceed 3%, and the combined feeder plus branch circuit drop does not exceed 5%.
  • NEC 215.2(A)(1) Informational Note No. 2 — Same voltage drop recommendation applied to feeder conductors.
  • NEC 230.42, 230.79(C), 230.90 — Specific requirements for this application, including circuit sizing, overcurrent protection, and installation methods.

Other Applications

Browse wire sizing guides for other common electrical circuits. Each page includes pre-computed wire sizes at multiple distances, installation tips, and NEC code references.