Voltage Drop Tables

480 volts three-phase is the standard power distribution voltage in industrial and large commercial facilities. The higher voltage reduces conductor size requirements by a factor of 4 compared to 120V for the same power delivery, making it the most efficient choice for large motors, industrial equipment, and long feeder runs. Power is typically distributed at 480V and then stepped down to 120/208V at local transformers for receptacles and lighting.

Understanding Voltage Drop at 480V

Voltage drop is the reduction in voltage between the source (panel) and the load (device) caused by the resistance of the conductors. At 480 volts, a 3% voltage drop equals 14.4 volts, meaning the voltage at the load would be 465.6 volts. The NEC recommends keeping voltage drop below 3% for branch circuits and below 5% for the combined feeder and branch circuit. While these are recommendations rather than mandatory requirements, they represent accepted engineering practice and are enforced by most electrical inspectors.

480V systems require arc flash labeling per NFPA 70E. Equipment and conductors must be rated for the higher voltage. Three-phase voltage drop calculations use the 1.732 factor.

Common 480V circuits include: Large industrial motors (50-500 HP), industrial welding equipment, large HVAC chillers, main distribution feeders, industrial compressors, CNC machines. Each of these applications has specific NEC requirements for wire sizing, overcurrent protection, and installation methods. The tables below provide voltage drop values for copper conductors at various distances and amperages, organized by wire gauge, so you can quickly determine whether a specific gauge is adequate for your installation.

Quick Reference: Maximum Distance by Gauge at 480V

The table below shows the maximum one-way distance for each copper wire gauge at common amperages to maintain a voltage drop of 3% or less at 480 volts (three phase). If your run distance exceeds these values, you must use a larger wire gauge.

Gauge 30A Max Dist50A Max Dist100A Max Dist150A Max Dist200A Max Dist
10 AWG 223 ft134 ft67 ft44 ft33 ft
8 AWG 356 ft213 ft106 ft71 ft53 ft
6 AWG 564 ft338 ft169 ft112 ft84 ft
4 AWG 899 ft539 ft269 ft179 ft134 ft
3 AWG 1131 ft678 ft339 ft226 ft169 ft
2 AWG 1428 ft857 ft428 ft285 ft214 ft
1 AWG 1799 ft1079 ft539 ft359 ft269 ft
1/0 AWG 2271 ft1362 ft681 ft454 ft340 ft
2/0 AWG 2865 ft1719 ft859 ft573 ft429 ft
3/0 AWG 3617 ft2170 ft1085 ft723 ft542 ft
4/0 AWG 4558 ft2734 ft1367 ft911 ft683 ft
250 kcmil 5381 ft3228 ft1614 ft1076 ft807 ft
300 kcmil 6460 ft3876 ft1938 ft1292 ft969 ft
350 kcmil 7551 ft4530 ft2265 ft1510 ft1132 ft
400 kcmil 8633 ft5180 ft2590 ft1726 ft1295 ft
500 kcmil 10741 ft6445 ft3222 ft2148 ft1611 ft

14 AWG Voltage Drop at 480V

Voltage drop values for 14 AWG copper conductor (3.14 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 20A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 4.1V
0.8%
6.8V
1.4%
13.6V
2.8%
20.4V
4.3%
27.2V
5.7%
50 ft 8.2V
1.7%
13.6V
2.8%
27.2V
5.7%
40.8V
8.5%
54.4V
11.3%
75 ft 12.2V
2.5%
20.4V
4.3%
40.8V
8.5%
61.2V
12.8%
81.6V
17.0%
100 ft 16.3V
3.4%
27.2V
5.7%
54.4V
11.3%
81.6V
17.0%
108.8V
22.7%
125 ft 20.4V
4.3%
34.0V
7.1%
68.0V
14.2%
102.0V
21.2%
136.0V
28.3%
150 ft 24.5V
5.1%
40.8V
8.5%
81.6V
17.0%
122.4V
25.5%
163.2V
34.0%
200 ft 32.6V
6.8%
54.4V
11.3%
108.8V
22.7%
163.2V
34.0%
217.5V
45.3%
250 ft 40.8V
8.5%
68.0V
14.2%
136.0V
28.3%
203.9V
42.5%
271.9V
56.6%
300 ft 49.0V
10.2%
81.6V
17.0%
163.2V
34.0%
244.7V
51.0%
326.3V
68.0%
400 ft 65.3V
13.6%
108.8V
22.7%
217.5V
45.3%
326.3V
68.0%
435.1V
90.6%
500 ft 81.6V
17.0%
136.0V
28.3%
271.9V
56.6%
407.9V
85.0%
543.9V
113.3%

12 AWG Voltage Drop at 480V

Voltage drop values for 12 AWG copper conductor (1.98 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 25A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 2.6V
0.5%
4.3V
0.9%
8.6V
1.8%
12.9V
2.7%
17.1V
3.6%
50 ft 5.1V
1.1%
8.6V
1.8%
17.1V
3.6%
25.7V
5.4%
34.3V
7.1%
75 ft 7.7V
1.6%
12.9V
2.7%
25.7V
5.4%
38.6V
8.0%
51.4V
10.7%
100 ft 10.3V
2.1%
17.1V
3.6%
34.3V
7.1%
51.4V
10.7%
68.6V
14.3%
125 ft 12.9V
2.7%
21.4V
4.5%
42.9V
8.9%
64.3V
13.4%
85.7V
17.9%
150 ft 15.4V
3.2%
25.7V
5.4%
51.4V
10.7%
77.2V
16.1%
102.9V
21.4%
200 ft 20.6V
4.3%
34.3V
7.1%
68.6V
14.3%
102.9V
21.4%
137.2V
28.6%
250 ft 25.7V
5.4%
42.9V
8.9%
85.7V
17.9%
128.6V
26.8%
171.5V
35.7%
300 ft 30.9V
6.4%
51.4V
10.7%
102.9V
21.4%
154.3V
32.1%
205.8V
42.9%
400 ft 41.1V
8.6%
68.6V
14.3%
137.2V
28.6%
205.8V
42.9%
274.4V
57.2%
500 ft 51.4V
10.7%
85.7V
17.9%
171.5V
35.7%
257.2V
53.6%
342.9V
71.4%

10 AWG Voltage Drop at 480V

Voltage drop values for 10 AWG copper conductor (1.24 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 35A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 1.6V
0.3%
2.7V
0.6%
5.4V
1.1%
8.1V
1.7%
10.7V
2.2%
50 ft 3.2V
0.7%
5.4V
1.1%
10.7V
2.2%
16.1V
3.4%
21.5V
4.5%
75 ft 4.8V
1.0%
8.1V
1.7%
16.1V
3.4%
24.2V
5.0%
32.2V
6.7%
100 ft 6.4V
1.3%
10.7V
2.2%
21.5V
4.5%
32.2V
6.7%
43.0V
8.9%
125 ft 8.1V
1.7%
13.4V
2.8%
26.9V
5.6%
40.3V
8.4%
53.7V
11.2%
150 ft 9.7V
2.0%
16.1V
3.4%
32.2V
6.7%
48.3V
10.1%
64.4V
13.4%
200 ft 12.9V
2.7%
21.5V
4.5%
43.0V
8.9%
64.4V
13.4%
85.9V
17.9%
250 ft 16.1V
3.4%
26.9V
5.6%
53.7V
11.2%
80.5V
16.8%
107.4V
22.4%
300 ft 19.3V
4.0%
32.2V
6.7%
64.4V
13.4%
96.7V
20.1%
128.9V
26.9%
400 ft 25.8V
5.4%
43.0V
8.9%
85.9V
17.9%
128.9V
26.9%
171.8V
35.8%
500 ft 32.2V
6.7%
53.7V
11.2%
107.4V
22.4%
161.1V
33.6%
214.8V
44.7%

8 AWG Voltage Drop at 480V

Voltage drop values for 8 AWG copper conductor (0.778 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 50A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 1.0V
0.2%
1.7V
0.3%
3.4V
0.7%
5.0V
1.1%
6.7V
1.4%
50 ft 2.0V
0.4%
3.4V
0.7%
6.7V
1.4%
10.1V
2.1%
13.5V
2.8%
75 ft 3.0V
0.6%
5.0V
1.1%
10.1V
2.1%
15.2V
3.2%
20.2V
4.2%
100 ft 4.0V
0.8%
6.7V
1.4%
13.5V
2.8%
20.2V
4.2%
26.9V
5.6%
125 ft 5.0V
1.1%
8.4V
1.8%
16.8V
3.5%
25.3V
5.3%
33.7V
7.0%
150 ft 6.1V
1.3%
10.1V
2.1%
20.2V
4.2%
30.3V
6.3%
40.4V
8.4%
200 ft 8.1V
1.7%
13.5V
2.8%
26.9V
5.6%
40.4V
8.4%
53.9V
11.2%
250 ft 10.1V
2.1%
16.8V
3.5%
33.7V
7.0%
50.5V
10.5%
67.4V
14.0%
300 ft 12.1V
2.5%
20.2V
4.2%
40.4V
8.4%
60.6V
12.6%
80.8V
16.8%
400 ft 16.2V
3.4%
26.9V
5.6%
53.9V
11.2%
80.8V
16.8%
107.8V
22.5%
500 ft 20.2V
4.2%
33.7V
7.0%
67.4V
14.0%
101.1V
21.1%
134.8V
28.1%

6 AWG Voltage Drop at 480V

Voltage drop values for 6 AWG copper conductor (0.491 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 65A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.6V
0.1%
1.1V
0.2%
2.1V
0.4%
3.2V
0.7%
4.3V
0.9%
50 ft 1.3V
0.3%
2.1V
0.4%
4.3V
0.9%
6.4V
1.3%
8.5V
1.8%
75 ft 1.9V
0.4%
3.2V
0.7%
6.4V
1.3%
9.6V
2.0%
12.8V
2.7%
100 ft 2.5V
0.5%
4.3V
0.9%
8.5V
1.8%
12.8V
2.7%
17.0V
3.5%
125 ft 3.2V
0.7%
5.3V
1.1%
10.6V
2.2%
15.9V
3.3%
21.3V
4.4%
150 ft 3.8V
0.8%
6.4V
1.3%
12.8V
2.7%
19.1V
4.0%
25.5V
5.3%
200 ft 5.1V
1.1%
8.5V
1.8%
17.0V
3.5%
25.5V
5.3%
34.0V
7.1%
250 ft 6.4V
1.3%
10.6V
2.2%
21.3V
4.4%
31.9V
6.6%
42.5V
8.9%
300 ft 7.7V
1.6%
12.8V
2.7%
25.5V
5.3%
38.3V
8.0%
51.0V
10.6%
400 ft 10.2V
2.1%
17.0V
3.5%
34.0V
7.1%
51.0V
10.6%
68.0V
14.2%
500 ft 12.8V
2.7%
21.3V
4.4%
42.5V
8.9%
63.8V
13.3%
85.0V
17.7%

4 AWG Voltage Drop at 480V

Voltage drop values for 4 AWG copper conductor (0.308 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 85A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.4V
0.1%
0.7V
0.1%
1.3V
0.3%
2.0V
0.4%
2.7V
0.6%
50 ft 0.8V
0.2%
1.3V
0.3%
2.7V
0.6%
4.0V
0.8%
5.3V
1.1%
75 ft 1.2V
0.3%
2.0V
0.4%
4.0V
0.8%
6.0V
1.3%
8.0V
1.7%
100 ft 1.6V
0.3%
2.7V
0.6%
5.3V
1.1%
8.0V
1.7%
10.7V
2.2%
125 ft 2.0V
0.4%
3.3V
0.7%
6.7V
1.4%
10.0V
2.1%
13.3V
2.8%
150 ft 2.4V
0.5%
4.0V
0.8%
8.0V
1.7%
12.0V
2.5%
16.0V
3.3%
200 ft 3.2V
0.7%
5.3V
1.1%
10.7V
2.2%
16.0V
3.3%
21.3V
4.5%
250 ft 4.0V
0.8%
6.7V
1.4%
13.3V
2.8%
20.0V
4.2%
26.7V
5.6%
300 ft 4.8V
1.0%
8.0V
1.7%
16.0V
3.3%
24.0V
5.0%
32.0V
6.7%
400 ft 6.4V
1.3%
10.7V
2.2%
21.3V
4.5%
32.0V
6.7%
42.7V
8.9%
500 ft 8.0V
1.7%
13.3V
2.8%
26.7V
5.6%
40.0V
8.3%
53.4V
11.1%

3 AWG Voltage Drop at 480V

Voltage drop values for 3 AWG copper conductor (0.245 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 100A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.3V
0.1%
0.5V
0.1%
1.1V
0.2%
1.6V
0.3%
2.1V
0.4%
50 ft 0.6V
0.1%
1.1V
0.2%
2.1V
0.4%
3.2V
0.7%
4.2V
0.9%
75 ft 0.9V
0.2%
1.6V
0.3%
3.2V
0.7%
4.8V
1.0%
6.4V
1.3%
100 ft 1.3V
0.3%
2.1V
0.4%
4.2V
0.9%
6.4V
1.3%
8.5V
1.8%
125 ft 1.6V
0.3%
2.6V
0.6%
5.3V
1.1%
8.0V
1.7%
10.6V
2.2%
150 ft 1.9V
0.4%
3.2V
0.7%
6.4V
1.3%
9.6V
2.0%
12.7V
2.6%
200 ft 2.5V
0.5%
4.2V
0.9%
8.5V
1.8%
12.7V
2.6%
17.0V
3.5%
250 ft 3.2V
0.7%
5.3V
1.1%
10.6V
2.2%
15.9V
3.3%
21.2V
4.4%
300 ft 3.8V
0.8%
6.4V
1.3%
12.7V
2.6%
19.1V
4.0%
25.5V
5.3%
400 ft 5.1V
1.1%
8.5V
1.8%
17.0V
3.5%
25.5V
5.3%
34.0V
7.1%
500 ft 6.4V
1.3%
10.6V
2.2%
21.2V
4.4%
31.8V
6.6%
42.4V
8.8%

2 AWG Voltage Drop at 480V

Voltage drop values for 2 AWG copper conductor (0.194 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 115A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.3V
0.1%
0.4V
0.1%
0.8V
0.2%
1.3V
0.3%
1.7V
0.3%
50 ft 0.5V
0.1%
0.8V
0.2%
1.7V
0.3%
2.5V
0.5%
3.4V
0.7%
75 ft 0.8V
0.2%
1.3V
0.3%
2.5V
0.5%
3.8V
0.8%
5.0V
1.1%
100 ft 1.0V
0.2%
1.7V
0.3%
3.4V
0.7%
5.0V
1.1%
6.7V
1.4%
125 ft 1.3V
0.3%
2.1V
0.4%
4.2V
0.9%
6.3V
1.3%
8.4V
1.8%
150 ft 1.5V
0.3%
2.5V
0.5%
5.0V
1.1%
7.6V
1.6%
10.1V
2.1%
200 ft 2.0V
0.4%
3.4V
0.7%
6.7V
1.4%
10.1V
2.1%
13.4V
2.8%
250 ft 2.5V
0.5%
4.2V
0.9%
8.4V
1.8%
12.6V
2.6%
16.8V
3.5%
300 ft 3.0V
0.6%
5.0V
1.1%
10.1V
2.1%
15.1V
3.1%
20.2V
4.2%
400 ft 4.0V
0.8%
6.7V
1.4%
13.4V
2.8%
20.2V
4.2%
26.9V
5.6%
500 ft 5.0V
1.1%
8.4V
1.8%
16.8V
3.5%
25.2V
5.3%
33.6V
7.0%

1 AWG Voltage Drop at 480V

Voltage drop values for 1 AWG copper conductor (0.154 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 130A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.2V
0.0%
0.3V
0.1%
0.7V
0.1%
1.0V
0.2%
1.3V
0.3%
50 ft 0.4V
0.1%
0.7V
0.1%
1.3V
0.3%
2.0V
0.4%
2.7V
0.6%
75 ft 0.6V
0.1%
1.0V
0.2%
2.0V
0.4%
3.0V
0.6%
4.0V
0.8%
100 ft 0.8V
0.2%
1.3V
0.3%
2.7V
0.6%
4.0V
0.8%
5.3V
1.1%
125 ft 1.0V
0.2%
1.7V
0.3%
3.3V
0.7%
5.0V
1.0%
6.7V
1.4%
150 ft 1.2V
0.3%
2.0V
0.4%
4.0V
0.8%
6.0V
1.3%
8.0V
1.7%
200 ft 1.6V
0.3%
2.7V
0.6%
5.3V
1.1%
8.0V
1.7%
10.7V
2.2%
250 ft 2.0V
0.4%
3.3V
0.7%
6.7V
1.4%
10.0V
2.1%
13.3V
2.8%
300 ft 2.4V
0.5%
4.0V
0.8%
8.0V
1.7%
12.0V
2.5%
16.0V
3.3%
400 ft 3.2V
0.7%
5.3V
1.1%
10.7V
2.2%
16.0V
3.3%
21.3V
4.5%
500 ft 4.0V
0.8%
6.7V
1.4%
13.3V
2.8%
20.0V
4.2%
26.7V
5.6%

1/0 AWG Voltage Drop at 480V

Voltage drop values for 1/0 AWG copper conductor (0.122 ohms/kft) at 480 volts, three phase. Ampacity at 75°C: 150A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.2V
0.0%
0.3V
0.1%
0.5V
0.1%
0.8V
0.2%
1.1V
0.2%
50 ft 0.3V
0.1%
0.5V
0.1%
1.1V
0.2%
1.6V
0.3%
2.1V
0.4%
75 ft 0.5V
0.1%
0.8V
0.2%
1.6V
0.3%
2.4V
0.5%
3.2V
0.7%
100 ft 0.6V
0.1%
1.1V
0.2%
2.1V
0.4%
3.2V
0.7%
4.2V
0.9%
125 ft 0.8V
0.2%
1.3V
0.3%
2.6V
0.6%
4.0V
0.8%
5.3V
1.1%
150 ft 0.9V
0.2%
1.6V
0.3%
3.2V
0.7%
4.8V
1.0%
6.3V
1.3%
200 ft 1.3V
0.3%
2.1V
0.4%
4.2V
0.9%
6.3V
1.3%
8.4V
1.8%
250 ft 1.6V
0.3%
2.6V
0.6%
5.3V
1.1%
7.9V
1.6%
10.6V
2.2%
300 ft 1.9V
0.4%
3.2V
0.7%
6.3V
1.3%
9.5V
2.0%
12.7V
2.6%
400 ft 2.5V
0.5%
4.2V
0.9%
8.4V
1.8%
12.7V
2.6%
16.9V
3.5%
500 ft 3.2V
0.7%
5.3V
1.1%
10.6V
2.2%
15.8V
3.3%
21.1V
4.4%

Other Voltage Levels

View voltage drop tables for other standard voltages. Higher voltages result in lower percentage voltage drop for the same absolute voltage loss, which allows longer conductor runs without upsizing.