Voltage Drop Tables

277 volts is derived from a 480/277V wye-connected transformer and is the standard voltage for commercial and industrial lighting in the United States. Using 277V for lighting reduces the current draw by more than half compared to 120V, allowing smaller wire sizes and longer circuit runs. LED and fluorescent lighting ballasts designed for 277V operation are standard in commercial construction.

Understanding Voltage Drop at 277V

Voltage drop is the reduction in voltage between the source (panel) and the load (device) caused by the resistance of the conductors. At 277 volts, a 3% voltage drop equals 8.3 volts, meaning the voltage at the load would be 268.7 volts. The NEC recommends keeping voltage drop below 3% for branch circuits and below 5% for the combined feeder and branch circuit. While these are recommendations rather than mandatory requirements, they represent accepted engineering practice and are enforced by most electrical inspectors.

NEC 210.6 permits 277V lighting circuits in commercial and industrial occupancies. Receptacles at 277V require specific configurations to prevent accidental connection of 120V equipment.

Common 277V circuits include: Commercial fluorescent lighting, LED high-bay lighting, parking lot lighting, warehouse lighting, office lighting circuits, industrial lighting. Each of these applications has specific NEC requirements for wire sizing, overcurrent protection, and installation methods. The tables below provide voltage drop values for copper conductors at various distances and amperages, organized by wire gauge, so you can quickly determine whether a specific gauge is adequate for your installation.

Quick Reference: Maximum Distance by Gauge at 277V

The table below shows the maximum one-way distance for each copper wire gauge at common amperages to maintain a voltage drop of 3% or less at 277 volts (single phase). If your run distance exceeds these values, you must use a larger wire gauge.

Gauge 30A Max Dist50A Max Dist100A Max Dist150A Max Dist200A Max Dist
10 AWG 111 ft67 ft33 ft22 ft16 ft
8 AWG 178 ft106 ft53 ft35 ft26 ft
6 AWG 282 ft169 ft84 ft56 ft42 ft
4 AWG 449 ft269 ft134 ft89 ft67 ft
3 AWG 565 ft339 ft169 ft113 ft84 ft
2 AWG 713 ft428 ft214 ft142 ft107 ft
1 AWG 899 ft539 ft269 ft179 ft134 ft
1/0 AWG 1135 ft681 ft340 ft227 ft170 ft
2/0 AWG 1432 ft859 ft429 ft286 ft214 ft
3/0 AWG 1808 ft1084 ft542 ft361 ft271 ft
4/0 AWG 2277 ft1366 ft683 ft455 ft341 ft
250 kcmil 2689 ft1613 ft806 ft537 ft403 ft
300 kcmil 3228 ft1937 ft968 ft645 ft484 ft
350 kcmil 3773 ft2264 ft1132 ft754 ft566 ft
400 kcmil 4314 ft2588 ft1294 ft862 ft647 ft
500 kcmil 5368 ft3220 ft1610 ft1073 ft805 ft

14 AWG Voltage Drop at 277V

Voltage drop values for 14 AWG copper conductor (3.14 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 20A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 4.7V
1.7%
7.8V
2.8%
15.7V
5.7%
23.6V
8.5%
31.4V
11.3%
50 ft 9.4V
3.4%
15.7V
5.7%
31.4V
11.3%
47.1V
17.0%
62.8V
22.7%
75 ft 14.1V
5.1%
23.6V
8.5%
47.1V
17.0%
70.7V
25.5%
94.2V
34.0%
100 ft 18.8V
6.8%
31.4V
11.3%
62.8V
22.7%
94.2V
34.0%
125.6V
45.3%
125 ft 23.6V
8.5%
39.3V
14.2%
78.5V
28.3%
117.8V
42.5%
157.0V
56.7%
150 ft 28.3V
10.2%
47.1V
17.0%
94.2V
34.0%
141.3V
51.0%
188.4V
68.0%
200 ft 37.7V
13.6%
62.8V
22.7%
125.6V
45.3%
188.4V
68.0%
251.2V
90.7%
250 ft 47.1V
17.0%
78.5V
28.3%
157.0V
56.7%
235.5V
85.0%
314.0V
113.4%
300 ft 56.5V
20.4%
94.2V
34.0%
188.4V
68.0%
282.6V
102.0%
376.8V
136.0%
400 ft 75.4V
27.2%
125.6V
45.3%
251.2V
90.7%
376.8V
136.0%
502.4V
181.4%
500 ft 94.2V
34.0%
157.0V
56.7%
314.0V
113.4%
471.0V
170.0%
628.0V
226.7%

12 AWG Voltage Drop at 277V

Voltage drop values for 12 AWG copper conductor (1.98 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 25A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 3.0V
1.1%
5.0V
1.8%
9.9V
3.6%
14.8V
5.4%
19.8V
7.2%
50 ft 5.9V
2.1%
9.9V
3.6%
19.8V
7.2%
29.7V
10.7%
39.6V
14.3%
75 ft 8.9V
3.2%
14.8V
5.4%
29.7V
10.7%
44.5V
16.1%
59.4V
21.4%
100 ft 11.9V
4.3%
19.8V
7.2%
39.6V
14.3%
59.4V
21.4%
79.2V
28.6%
125 ft 14.8V
5.4%
24.8V
8.9%
49.5V
17.9%
74.3V
26.8%
99.0V
35.7%
150 ft 17.8V
6.4%
29.7V
10.7%
59.4V
21.4%
89.1V
32.2%
118.8V
42.9%
200 ft 23.8V
8.6%
39.6V
14.3%
79.2V
28.6%
118.8V
42.9%
158.4V
57.2%
250 ft 29.7V
10.7%
49.5V
17.9%
99.0V
35.7%
148.5V
53.6%
198.0V
71.5%
300 ft 35.6V
12.9%
59.4V
21.4%
118.8V
42.9%
178.2V
64.3%
237.6V
85.8%
400 ft 47.5V
17.2%
79.2V
28.6%
158.4V
57.2%
237.6V
85.8%
316.8V
114.4%
500 ft 59.4V
21.4%
99.0V
35.7%
198.0V
71.5%
297.0V
107.2%
396.0V
143.0%

10 AWG Voltage Drop at 277V

Voltage drop values for 10 AWG copper conductor (1.24 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 35A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 1.9V
0.7%
3.1V
1.1%
6.2V
2.2%
9.3V
3.4%
12.4V
4.5%
50 ft 3.7V
1.3%
6.2V
2.2%
12.4V
4.5%
18.6V
6.7%
24.8V
8.9%
75 ft 5.6V
2.0%
9.3V
3.4%
18.6V
6.7%
27.9V
10.1%
37.2V
13.4%
100 ft 7.4V
2.7%
12.4V
4.5%
24.8V
8.9%
37.2V
13.4%
49.6V
17.9%
125 ft 9.3V
3.4%
15.5V
5.6%
31.0V
11.2%
46.5V
16.8%
62.0V
22.4%
150 ft 11.2V
4.0%
18.6V
6.7%
37.2V
13.4%
55.8V
20.1%
74.4V
26.9%
200 ft 14.9V
5.4%
24.8V
8.9%
49.6V
17.9%
74.4V
26.9%
99.2V
35.8%
250 ft 18.6V
6.7%
31.0V
11.2%
62.0V
22.4%
93.0V
33.6%
124.0V
44.8%
300 ft 22.3V
8.1%
37.2V
13.4%
74.4V
26.9%
111.6V
40.3%
148.8V
53.7%
400 ft 29.8V
10.7%
49.6V
17.9%
99.2V
35.8%
148.8V
53.7%
198.4V
71.6%
500 ft 37.2V
13.4%
62.0V
22.4%
124.0V
44.8%
186.0V
67.2%
248.0V
89.5%

8 AWG Voltage Drop at 277V

Voltage drop values for 8 AWG copper conductor (0.778 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 50A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 1.2V
0.4%
1.9V
0.7%
3.9V
1.4%
5.8V
2.1%
7.8V
2.8%
50 ft 2.3V
0.8%
3.9V
1.4%
7.8V
2.8%
11.7V
4.2%
15.6V
5.6%
75 ft 3.5V
1.3%
5.8V
2.1%
11.7V
4.2%
17.5V
6.3%
23.3V
8.4%
100 ft 4.7V
1.7%
7.8V
2.8%
15.6V
5.6%
23.3V
8.4%
31.1V
11.2%
125 ft 5.8V
2.1%
9.7V
3.5%
19.4V
7.0%
29.2V
10.5%
38.9V
14.0%
150 ft 7.0V
2.5%
11.7V
4.2%
23.3V
8.4%
35.0V
12.6%
46.7V
16.9%
200 ft 9.3V
3.4%
15.6V
5.6%
31.1V
11.2%
46.7V
16.9%
62.2V
22.5%
250 ft 11.7V
4.2%
19.4V
7.0%
38.9V
14.0%
58.4V
21.1%
77.8V
28.1%
300 ft 14.0V
5.1%
23.3V
8.4%
46.7V
16.9%
70.0V
25.3%
93.4V
33.7%
400 ft 18.7V
6.7%
31.1V
11.2%
62.2V
22.5%
93.4V
33.7%
124.5V
44.9%
500 ft 23.3V
8.4%
38.9V
14.0%
77.8V
28.1%
116.7V
42.1%
155.6V
56.2%

6 AWG Voltage Drop at 277V

Voltage drop values for 6 AWG copper conductor (0.491 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 65A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.7V
0.3%
1.2V
0.4%
2.5V
0.9%
3.7V
1.3%
4.9V
1.8%
50 ft 1.5V
0.5%
2.5V
0.9%
4.9V
1.8%
7.4V
2.7%
9.8V
3.5%
75 ft 2.2V
0.8%
3.7V
1.3%
7.4V
2.7%
11.1V
4.0%
14.7V
5.3%
100 ft 3.0V
1.1%
4.9V
1.8%
9.8V
3.5%
14.7V
5.3%
19.6V
7.1%
125 ft 3.7V
1.3%
6.1V
2.2%
12.3V
4.4%
18.4V
6.7%
24.6V
8.9%
150 ft 4.4V
1.6%
7.4V
2.7%
14.7V
5.3%
22.1V
8.0%
29.5V
10.6%
200 ft 5.9V
2.1%
9.8V
3.5%
19.6V
7.1%
29.5V
10.6%
39.3V
14.2%
250 ft 7.4V
2.7%
12.3V
4.4%
24.6V
8.9%
36.8V
13.3%
49.1V
17.7%
300 ft 8.8V
3.2%
14.7V
5.3%
29.5V
10.6%
44.2V
15.9%
58.9V
21.3%
400 ft 11.8V
4.3%
19.6V
7.1%
39.3V
14.2%
58.9V
21.3%
78.6V
28.4%
500 ft 14.7V
5.3%
24.6V
8.9%
49.1V
17.7%
73.7V
26.6%
98.2V
35.5%

4 AWG Voltage Drop at 277V

Voltage drop values for 4 AWG copper conductor (0.308 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 85A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.5V
0.2%
0.8V
0.3%
1.5V
0.6%
2.3V
0.8%
3.1V
1.1%
50 ft 0.9V
0.3%
1.5V
0.6%
3.1V
1.1%
4.6V
1.7%
6.2V
2.2%
75 ft 1.4V
0.5%
2.3V
0.8%
4.6V
1.7%
6.9V
2.5%
9.2V
3.3%
100 ft 1.9V
0.7%
3.1V
1.1%
6.2V
2.2%
9.2V
3.3%
12.3V
4.5%
125 ft 2.3V
0.8%
3.9V
1.4%
7.7V
2.8%
11.6V
4.2%
15.4V
5.6%
150 ft 2.8V
1.0%
4.6V
1.7%
9.2V
3.3%
13.9V
5.0%
18.5V
6.7%
200 ft 3.7V
1.3%
6.2V
2.2%
12.3V
4.5%
18.5V
6.7%
24.6V
8.9%
250 ft 4.6V
1.7%
7.7V
2.8%
15.4V
5.6%
23.1V
8.3%
30.8V
11.1%
300 ft 5.5V
2.0%
9.2V
3.3%
18.5V
6.7%
27.7V
10.0%
37.0V
13.3%
400 ft 7.4V
2.7%
12.3V
4.5%
24.6V
8.9%
37.0V
13.3%
49.3V
17.8%
500 ft 9.2V
3.3%
15.4V
5.6%
30.8V
11.1%
46.2V
16.7%
61.6V
22.2%

3 AWG Voltage Drop at 277V

Voltage drop values for 3 AWG copper conductor (0.245 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 100A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.4V
0.1%
0.6V
0.2%
1.2V
0.4%
1.8V
0.7%
2.5V
0.9%
50 ft 0.7V
0.3%
1.2V
0.4%
2.5V
0.9%
3.7V
1.3%
4.9V
1.8%
75 ft 1.1V
0.4%
1.8V
0.7%
3.7V
1.3%
5.5V
2.0%
7.3V
2.6%
100 ft 1.5V
0.5%
2.5V
0.9%
4.9V
1.8%
7.3V
2.6%
9.8V
3.5%
125 ft 1.8V
0.7%
3.1V
1.1%
6.1V
2.2%
9.2V
3.3%
12.3V
4.4%
150 ft 2.2V
0.8%
3.7V
1.3%
7.3V
2.6%
11.0V
4.0%
14.7V
5.3%
200 ft 2.9V
1.1%
4.9V
1.8%
9.8V
3.5%
14.7V
5.3%
19.6V
7.1%
250 ft 3.7V
1.3%
6.1V
2.2%
12.3V
4.4%
18.4V
6.6%
24.5V
8.8%
300 ft 4.4V
1.6%
7.3V
2.6%
14.7V
5.3%
22.1V
8.0%
29.4V
10.6%
400 ft 5.9V
2.1%
9.8V
3.5%
19.6V
7.1%
29.4V
10.6%
39.2V
14.2%
500 ft 7.3V
2.6%
12.3V
4.4%
24.5V
8.8%
36.8V
13.3%
49.0V
17.7%

2 AWG Voltage Drop at 277V

Voltage drop values for 2 AWG copper conductor (0.194 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 115A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.3V
0.1%
0.5V
0.2%
1.0V
0.3%
1.5V
0.5%
1.9V
0.7%
50 ft 0.6V
0.2%
1.0V
0.3%
1.9V
0.7%
2.9V
1.1%
3.9V
1.4%
75 ft 0.9V
0.3%
1.5V
0.5%
2.9V
1.1%
4.4V
1.6%
5.8V
2.1%
100 ft 1.2V
0.4%
1.9V
0.7%
3.9V
1.4%
5.8V
2.1%
7.8V
2.8%
125 ft 1.5V
0.5%
2.4V
0.9%
4.8V
1.8%
7.3V
2.6%
9.7V
3.5%
150 ft 1.8V
0.6%
2.9V
1.1%
5.8V
2.1%
8.7V
3.1%
11.6V
4.2%
200 ft 2.3V
0.8%
3.9V
1.4%
7.8V
2.8%
11.6V
4.2%
15.5V
5.6%
250 ft 2.9V
1.1%
4.8V
1.8%
9.7V
3.5%
14.6V
5.3%
19.4V
7.0%
300 ft 3.5V
1.3%
5.8V
2.1%
11.6V
4.2%
17.5V
6.3%
23.3V
8.4%
400 ft 4.7V
1.7%
7.8V
2.8%
15.5V
5.6%
23.3V
8.4%
31.0V
11.2%
500 ft 5.8V
2.1%
9.7V
3.5%
19.4V
7.0%
29.1V
10.5%
38.8V
14.0%

1 AWG Voltage Drop at 277V

Voltage drop values for 1 AWG copper conductor (0.154 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 130A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.2V
0.1%
0.4V
0.1%
0.8V
0.3%
1.2V
0.4%
1.5V
0.6%
50 ft 0.5V
0.2%
0.8V
0.3%
1.5V
0.6%
2.3V
0.8%
3.1V
1.1%
75 ft 0.7V
0.3%
1.2V
0.4%
2.3V
0.8%
3.5V
1.3%
4.6V
1.7%
100 ft 0.9V
0.3%
1.5V
0.6%
3.1V
1.1%
4.6V
1.7%
6.2V
2.2%
125 ft 1.2V
0.4%
1.9V
0.7%
3.9V
1.4%
5.8V
2.1%
7.7V
2.8%
150 ft 1.4V
0.5%
2.3V
0.8%
4.6V
1.7%
6.9V
2.5%
9.2V
3.3%
200 ft 1.9V
0.7%
3.1V
1.1%
6.2V
2.2%
9.2V
3.3%
12.3V
4.5%
250 ft 2.3V
0.8%
3.9V
1.4%
7.7V
2.8%
11.6V
4.2%
15.4V
5.6%
300 ft 2.8V
1.0%
4.6V
1.7%
9.2V
3.3%
13.9V
5.0%
18.5V
6.7%
400 ft 3.7V
1.3%
6.2V
2.2%
12.3V
4.5%
18.5V
6.7%
24.6V
8.9%
500 ft 4.6V
1.7%
7.7V
2.8%
15.4V
5.6%
23.1V
8.3%
30.8V
11.1%

1/0 AWG Voltage Drop at 277V

Voltage drop values for 1/0 AWG copper conductor (0.122 ohms/kft) at 277 volts, single phase. Ampacity at 75°C: 150A. Cells in red exceed the 3% NEC recommendation.

Distance 30A50A100A150A200A
25 ft 0.2V
0.1%
0.3V
0.1%
0.6V
0.2%
0.9V
0.3%
1.2V
0.4%
50 ft 0.4V
0.1%
0.6V
0.2%
1.2V
0.4%
1.8V
0.7%
2.4V
0.9%
75 ft 0.6V
0.2%
0.9V
0.3%
1.8V
0.7%
2.8V
1.0%
3.7V
1.3%
100 ft 0.7V
0.3%
1.2V
0.4%
2.4V
0.9%
3.7V
1.3%
4.9V
1.8%
125 ft 0.9V
0.3%
1.5V
0.6%
3.0V
1.1%
4.6V
1.6%
6.1V
2.2%
150 ft 1.1V
0.4%
1.8V
0.7%
3.7V
1.3%
5.5V
2.0%
7.3V
2.6%
200 ft 1.5V
0.5%
2.4V
0.9%
4.9V
1.8%
7.3V
2.6%
9.8V
3.5%
250 ft 1.8V
0.7%
3.0V
1.1%
6.1V
2.2%
9.2V
3.3%
12.2V
4.4%
300 ft 2.2V
0.8%
3.7V
1.3%
7.3V
2.6%
11.0V
4.0%
14.6V
5.3%
400 ft 2.9V
1.1%
4.9V
1.8%
9.8V
3.5%
14.6V
5.3%
19.5V
7.0%
500 ft 3.7V
1.3%
6.1V
2.2%
12.2V
4.4%
18.3V
6.6%
24.4V
8.8%

Other Voltage Levels

View voltage drop tables for other standard voltages. Higher voltages result in lower percentage voltage drop for the same absolute voltage loss, which allows longer conductor runs without upsizing.