Skip to content

Wire Size at 125 Feet (125 ft)

A 125-foot conductor run is typical for circuits to medium-distance outbuildings, detached garages set back from the house, well pumps near the property, and RV parking pads. At this distance, nearly all 120-volt circuits require wire larger than the NEC minimum for ampacity alone, and even 240-volt circuits with moderate current draw need careful voltage drop analysis.

Voltage Drop at 125 Feet

At a distance of 125 feet, the voltage drop across any conductor is proportional to the current draw, the conductor resistance, and the type of circuit (single-phase or three-phase). On a 120-volt single-phase circuit, the 3% limit allows a maximum of 3.6 volts of drop. On a 240-volt circuit, the 3% limit allows 7.2 volts. The tables below show the recommended wire gauge for every common voltage and amperage combination at exactly 125 feet, making it easy to find the right conductor without performing manual calculations.

The recommendations consider both ampacity (from NEC Table 310.16 at 75 degrees C) and voltage drop (using NEC Chapter 9, Table 8 resistance values). The recommended gauge is the smallest standard size that satisfies both requirements simultaneously. When the 3% column and 5% column show different gauges, voltage drop is the controlling factor, and you may be able to use the smaller gauge if your circuit qualifies for the 5% combined feeder-plus-branch limit.

120V Wire Sizes at 125 ft

Recommended wire gauges for 120-volt circuits at a one-way distance of 125 feet. The copper columns show the recommended gauge at both 3% and 5% voltage drop limits. The aluminum column shows the 3% recommendation, which is typically one to two sizes larger than copper.

Amps Copper (3%) Cu V-Drop Copper (5%) Cu V-Drop Aluminum (3%) Al V-Drop
15A 8 AWG 2.43% 10 AWG 3.88% 6 AWG 2.53%
20A 6 AWG 2.05% 8 AWG 3.24% 4 AWG 2.12%
30A 4 AWG 1.93% 8 AWG 4.86% 3 AWG 2.52%

240V Wire Sizes at 125 ft

Recommended wire gauges for 240-volt circuits at a one-way distance of 125 feet. The copper columns show the recommended gauge at both 3% and 5% voltage drop limits. The aluminum column shows the 3% recommendation, which is typically one to two sizes larger than copper.

Amps Copper (3%) Cu V-Drop Copper (5%) Cu V-Drop Aluminum (3%) Al V-Drop
15A 10 AWG 1.94% 14 AWG 4.91% 8 AWG 2.00%
20A 10 AWG 2.58% 12 AWG 4.13% 8 AWG 2.67%
30A 8 AWG 2.43% 10 AWG 3.88% 6 AWG 2.53%
40A 6 AWG 2.05% 8 AWG 3.24% 4 AWG 2.12%
50A 6 AWG 2.56% 8 AWG 4.05% 4 AWG 2.65%
60A 4 AWG 1.93% 6 AWG 3.07% 3 AWG 2.52%
80A 4 AWG 2.57% 4 AWG 2.57% 2 AWG 2.66%
100A 3 AWG 2.55% 3 AWG 2.55% 1 AWG 2.64%
150A 1/0 AWG 1.91% 1/0 AWG 1.91% 3/0 AWG 1.97%
200A 3/0 AWG 1.60% 3/0 AWG 1.60% 250 kcmil 1.76%

208V Wire Sizes at 125 ft

Recommended wire gauges for 208-volt circuits at a one-way distance of 125 feet. The copper columns show the recommended gauge at both 3% and 5% voltage drop limits. The aluminum column shows the 3% recommendation, which is typically one to two sizes larger than copper.

Amps Copper (3%) Cu V-Drop Copper (5%) Cu V-Drop Aluminum (3%) Al V-Drop
15A 10 AWG 1.94% 14 AWG 4.90% 8 AWG 2.00%
20A 10 AWG 2.58% 12 AWG 4.12% 8 AWG 2.66%
30A 8 AWG 2.43% 10 AWG 3.87% 6 AWG 2.52%
40A 6 AWG 2.04% 8 AWG 3.24% 4 AWG 2.12%
50A 6 AWG 2.56% 8 AWG 4.05% 4 AWG 2.64%
60A 4 AWG 1.92% 6 AWG 3.07% 3 AWG 2.52%
80A 4 AWG 2.56% 4 AWG 2.56% 2 AWG 2.66%
100A 3 AWG 2.55% 3 AWG 2.55% 1 AWG 2.63%
150A 1/0 AWG 1.90% 1/0 AWG 1.90% 3/0 AWG 1.97%
200A 3/0 AWG 1.59% 3/0 AWG 1.59% 250 kcmil 1.76%

277V Wire Sizes at 125 ft

Recommended wire gauges for 277-volt circuits at a one-way distance of 125 feet. The copper columns show the recommended gauge at both 3% and 5% voltage drop limits. The aluminum column shows the 3% recommendation, which is typically one to two sizes larger than copper.

Amps Copper (3%) Cu V-Drop Copper (5%) Cu V-Drop Aluminum (3%) Al V-Drop
15A 12 AWG 2.32% 14 AWG 3.68% 10 AWG 2.39%
20A 10 AWG 1.94% 14 AWG 4.91% 8 AWG 2.00%
30A 10 AWG 2.91% 10 AWG 2.91% 6 AWG 1.89%
40A 8 AWG 2.43% 8 AWG 2.43% 6 AWG 2.53%
50A 6 AWG 1.92% 8 AWG 3.04% 4 AWG 1.99%
60A 6 AWG 2.30% 6 AWG 2.30% 4 AWG 2.38%
80A 4 AWG 1.93% 4 AWG 1.93% 3 AWG 2.52%
100A 3 AWG 1.91% 3 AWG 1.91% 1 AWG 1.98%
150A 1/0 AWG 1.43% 1/0 AWG 1.43% 3/0 AWG 1.48%
200A 3/0 AWG 1.20% 3/0 AWG 1.20% 250 kcmil 1.32%

480V Wire Sizes at 125 ft

Recommended wire gauges for 480-volt circuits at a one-way distance of 125 feet. The copper columns show the recommended gauge at both 3% and 5% voltage drop limits. The aluminum column shows the 3% recommendation, which is typically one to two sizes larger than copper.

Amps Copper (3%) Cu V-Drop Copper (5%) Cu V-Drop Aluminum (3%) Al V-Drop
15A 14 AWG 2.12% 14 AWG 2.12% 12 AWG 2.20%
20A 14 AWG 2.83% 14 AWG 2.83% 12 AWG 2.93%
30A 10 AWG 1.68% 10 AWG 1.68% 8 AWG 1.73%
40A 8 AWG 1.40% 8 AWG 1.40% 8 AWG 2.31%
50A 8 AWG 1.75% 8 AWG 1.75% 6 AWG 1.82%
60A 6 AWG 1.33% 6 AWG 1.33% 4 AWG 1.37%
80A 4 AWG 1.11% 4 AWG 1.11% 3 AWG 1.45%
100A 3 AWG 1.11% 3 AWG 1.11% 1 AWG 1.14%
150A 1/0 AWG 0.83% 1/0 AWG 0.83% 3/0 AWG 0.85%
200A 3/0 AWG 0.69% 3/0 AWG 0.69% 250 kcmil 0.76%

Tips for 125-Foot Runs

At 125 feet, voltage drop is a significant concern for most circuits and often requires upsizing the conductor beyond what ampacity alone would dictate. For 120-volt circuits, expect to use wire one to three sizes larger than the NEC minimum. For 240-volt circuits, the higher voltage provides some relief, but runs of 40 amps or more will still require careful analysis. Consider using aluminum conductors for feeders at this distance to reduce material costs.

When burying conductors for outdoor runs of 125 feet, use UF cable for direct burial or install individual conductors in PVC conduit. Direct burial cable must be installed at a minimum depth of 24 inches for 120V circuits (18 inches under a 2-inch concrete slab or under a residential driveway) per NEC Table 300.5. PVC conduit reduces the burial depth requirement to 18 inches. For long runs, the cost of trenching and backfill is often more significant than the conductor cost, so there is little reason not to upsize the conductor while the trench is open.

For above-ground runs to detached structures, the conductor must be supported and protected per NEC requirements. Overhead spans require a minimum clearance of 10 feet above finished grade, 12 feet above driveways, and 18 feet above public streets. Underground installation is generally preferred for permanent structures. Always install a grounding electrode system at the detached structure per NEC 250.32.

Other Distances

Browse wire sizing recommendations for other common run distances. As distance increases, voltage drop grows linearly, and the required conductor size increases to compensate.

Tools and Training for Electricians

Quality resources for your next wiring project.

Some links above are affiliate links — if you buy through them we may earn a small commission at no extra cost to you. As an Amazon Associate we earn from qualifying purchases.