8 AWG Voltage Drop at 480V 3-Phase

This page provides detailed voltage drop analysis for 8 AWG conductors operating at 480V 3-Phase (three-phase). The 8 AWG copper conductor has a resistance of 0.778 ohms per 1000 feet and an ampacity of 50 amps at 75 degrees C per NEC Table 310.16. Use the tables below to determine the voltage drop at any distance and amperage combination, or to find the maximum distance you can run 8 AWG wire while staying within the NEC recommended voltage drop limits.

Wire Gauge
8 AWG
Voltage
480V 3-Phase
Cu Ampacity
50A
Cu Resistance
0.778 Ω/kft

Maximum Distance for 8 AWG at 480V 3-Phase

The table below shows the maximum one-way distance you can run 8 AWG copper conductor at 480V 3-Phase for each amperage level while maintaining voltage drop at or below 3% (branch circuit) and 5% (feeder + branch combined). If your planned run exceeds these distances, you must use a larger wire gauge. These values assume three-phase power with a 1.732 multiplier in the voltage drop formula.

Amperage Max Distance (3%) Max Distance (5%) 3% Drop = 14.4V
5A 2137 ft 3562 ft 14.4 V
10A 1068 ft 1781 ft 14.4 V
15A 712 ft 1187 ft 14.4 V
20A 534 ft 890 ft 14.4 V
25A 427 ft 712 ft 14.4 V
30A 356 ft 593 ft 14.4 V
40A 267 ft 445 ft 14.4 V
50A 213 ft 356 ft 14.4 V
60A (exceeds ampacity) 178 ft 296 ft 14.4 V

Voltage Drop Table — 8 AWG Copper at 480V 3-Phase

Complete voltage drop matrix for 8 AWG copper conductor at 480V 3-Phase. Each cell shows the voltage drop in volts and percentage. Cells in red exceed the 3% NEC recommendation for branch circuits. Cells within the green range are NEC compliant. This table uses the three-phase voltage drop formula with a conductor resistance of 0.778 ohms per 1000 feet.

Distance 5A10A15A20A25A30A40A50A60A
25 ft 0.2V
0.0%
0.3V
0.1%
0.5V
0.1%
0.7V
0.1%
0.8V
0.2%
1.0V
0.2%
1.4V
0.3%
1.7V
0.3%
2.0V
0.4%
50 ft 0.3V
0.1%
0.7V
0.1%
1.0V
0.2%
1.4V
0.3%
1.7V
0.3%
2.0V
0.4%
2.7V
0.6%
3.4V
0.7%
4.0V
0.8%
75 ft 0.5V
0.1%
1.0V
0.2%
1.5V
0.3%
2.0V
0.4%
2.5V
0.5%
3.0V
0.6%
4.0V
0.8%
5.0V
1.1%
6.1V
1.3%
100 ft 0.7V
0.1%
1.4V
0.3%
2.0V
0.4%
2.7V
0.6%
3.4V
0.7%
4.0V
0.8%
5.4V
1.1%
6.7V
1.4%
8.1V
1.7%
125 ft 0.8V
0.2%
1.7V
0.3%
2.5V
0.5%
3.4V
0.7%
4.2V
0.9%
5.0V
1.1%
6.7V
1.4%
8.4V
1.8%
10.1V
2.1%
150 ft 1.0V
0.2%
2.0V
0.4%
3.0V
0.6%
4.0V
0.8%
5.0V
1.1%
6.1V
1.3%
8.1V
1.7%
10.1V
2.1%
12.1V
2.5%
200 ft 1.4V
0.3%
2.7V
0.6%
4.0V
0.8%
5.4V
1.1%
6.7V
1.4%
8.1V
1.7%
10.8V
2.3%
13.5V
2.8%
16.2V
3.4%
250 ft 1.7V
0.3%
3.4V
0.7%
5.0V
1.1%
6.7V
1.4%
8.4V
1.8%
10.1V
2.1%
13.5V
2.8%
16.8V
3.5%
20.2V
4.2%
300 ft 2.0V
0.4%
4.0V
0.8%
6.1V
1.3%
8.1V
1.7%
10.1V
2.1%
12.1V
2.5%
16.2V
3.4%
20.2V
4.2%
24.3V
5.0%
400 ft 2.7V
0.6%
5.4V
1.1%
8.1V
1.7%
10.8V
2.3%
13.5V
2.8%
16.2V
3.4%
21.6V
4.5%
26.9V
5.6%
32.3V
6.7%
500 ft 3.4V
0.7%
6.7V
1.4%
10.1V
2.1%
13.5V
2.8%
16.8V
3.5%
20.2V
4.2%
26.9V
5.6%
33.7V
7.0%
40.4V
8.4%

When to Use 8 AWG at 480V 3-Phase

8 AWG wire at 480V 3-Phase is appropriate for circuits where the amperage does not exceed 50 amps (copper, 75 degrees C) and the voltage drop at the planned distance stays within NEC recommendations. At short distances under 267 feet, 8 AWG handles 40-amp loads with comfortable voltage drop margin. As the distance increases, the voltage drop grows proportionally, and at some point a larger gauge becomes necessary.

If 8 AWG does not provide adequate voltage drop performance for your run distance, consider the next larger gauge. Each step up in wire size roughly doubles the maximum distance for the same voltage drop percentage. Alternatively, if the circuit operates at 120 volts and the distance is problematic, consider whether the load can be served by a 240-volt circuit instead, which halves the percentage voltage drop and doubles the effective run distance for the same wire gauge.

For aluminum conductors, 8 AWG has an ampacity of 40 amps at 75 degrees C and a resistance of 1.28 ohms per 1000 feet. The higher resistance means aluminum requires approximately 65% more distance correction compared to copper, often requiring an increase of one or two gauge sizes to match copper's voltage drop performance at the same distance.

Related Wire Sizes at 480V 3-Phase

Compare voltage drop performance across different wire gauges at 480V 3-Phase. Larger gauges have lower resistance and can run longer distances with less voltage drop.