500 kcmil Voltage Drop at 240V
This page provides detailed voltage drop analysis for 500 kcmil conductors operating at 240V (single-phase). The 500 kcmil copper conductor has a resistance of 0.0258 ohms per 1000 feet and an ampacity of 380 amps at 75 degrees C per NEC Table 310.16. Use the tables below to determine the voltage drop at any distance and amperage combination, or to find the maximum distance you can run 500 kcmil wire while staying within the NEC recommended voltage drop limits.
Maximum Distance for 500 kcmil at 240V
The table below shows the maximum one-way distance you can run 500 kcmil copper conductor at 240V for each amperage level while maintaining voltage drop at or below 3% (branch circuit) and 5% (feeder + branch combined). If your planned run exceeds these distances, you must use a larger wire gauge. These values assume single-phase power with a 2 multiplier in the voltage drop formula.
| Amperage | Max Distance (3%) | Max Distance (5%) | 3% Drop = 7.2V |
|---|---|---|---|
| 5A | 27906 ft | 46511 ft | 7.2 V |
| 10A | 13953 ft | 23255 ft | 7.2 V |
| 15A | 9302 ft | 15503 ft | 7.2 V |
| 20A | 6976 ft | 11627 ft | 7.2 V |
| 25A | 5581 ft | 9302 ft | 7.2 V |
| 30A | 4651 ft | 7751 ft | 7.2 V |
| 40A | 3488 ft | 5813 ft | 7.2 V |
| 50A | 2790 ft | 4651 ft | 7.2 V |
| 60A | 2325 ft | 3875 ft | 7.2 V |
| 80A | 1744 ft | 2906 ft | 7.2 V |
| 100A | 1395 ft | 2325 ft | 7.2 V |
Voltage Drop Table — 500 kcmil Copper at 240V
Complete voltage drop matrix for 500 kcmil copper conductor at 240V. Each cell shows the voltage drop in volts and percentage. Cells in red exceed the 3% NEC recommendation for branch circuits. Cells within the green range are NEC compliant. This table uses the single-phase voltage drop formula with a conductor resistance of 0.0258 ohms per 1000 feet.
| Distance | 5A | 10A | 15A | 20A | 25A | 30A | 40A | 50A | 60A | 80A | 100A |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 25 ft | 0.0V 0.0% | 0.0V 0.0% | 0.0V 0.0% | 0.0V 0.0% | 0.0V 0.0% | 0.0V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.1% |
| 50 ft | 0.0V 0.0% | 0.0V 0.0% | 0.0V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.1% | 0.3V 0.1% |
| 75 ft | 0.0V 0.0% | 0.0V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.4V 0.2% |
| 100 ft | 0.0V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% |
| 125 ft | 0.0V 0.0% | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.1% | 0.2V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.7V 0.3% |
| 150 ft | 0.0V 0.0% | 0.1V 0.0% | 0.1V 0.1% | 0.1V 0.1% | 0.2V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.6V 0.3% | 0.8V 0.3% |
| 200 ft | 0.1V 0.0% | 0.1V 0.0% | 0.1V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.6V 0.3% | 0.8V 0.3% | 1.0V 0.4% |
| 250 ft | 0.1V 0.0% | 0.1V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.7V 0.3% | 0.8V 0.3% | 1.0V 0.4% | 1.3V 0.5% |
| 300 ft | 0.1V 0.0% | 0.1V 0.1% | 0.2V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.6V 0.3% | 0.8V 0.3% | 0.9V 0.4% | 1.2V 0.5% | 1.6V 0.7% |
| 400 ft | 0.1V 0.0% | 0.2V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.6V 0.3% | 0.8V 0.3% | 1.0V 0.4% | 1.2V 0.5% | 1.6V 0.7% | 2.1V 0.9% |
| 500 ft | 0.1V 0.1% | 0.3V 0.1% | 0.4V 0.2% | 0.5V 0.2% | 0.7V 0.3% | 0.8V 0.3% | 1.0V 0.4% | 1.3V 0.5% | 1.6V 0.7% | 2.1V 0.9% | 2.6V 1.1% |
When to Use 500 kcmil at 240V
500 kcmil wire at 240V is appropriate for circuits where the amperage does not exceed 380 amps (copper, 75 degrees C) and the voltage drop at the planned distance stays within NEC recommendations. At short distances under 50 feet, 500 kcmil handles 304-amp loads with comfortable voltage drop margin. As the distance increases, the voltage drop grows proportionally, and at some point a larger gauge becomes necessary.
If 500 kcmil does not provide adequate voltage drop performance for your run distance, consider the next larger gauge. Each step up in wire size roughly doubles the maximum distance for the same voltage drop percentage. Alternatively, if the circuit operates at 120 volts and the distance is problematic, consider whether the load can be served by a 240-volt circuit instead, which halves the percentage voltage drop and doubles the effective run distance for the same wire gauge.
For aluminum conductors, 500 kcmil has an ampacity of 304 amps at 75 degrees C and a resistance of 0.0424 ohms per 1000 feet. The higher resistance means aluminum requires approximately 64% more distance correction compared to copper, often requiring an increase of one or two gauge sizes to match copper's voltage drop performance at the same distance.
Related Wire Sizes at 240V
Compare voltage drop performance across different wire gauges at 240V. Larger gauges have lower resistance and can run longer distances with less voltage drop.
Tools and Training for Electricians
Quality resources for your next wiring project.
Some links above are affiliate links — if you buy through them we may earn a small commission at no extra cost to you. As an Amazon Associate we earn from qualifying purchases.