Skip to content

4 AWG Voltage Drop at 480V 3-Phase

This page provides detailed voltage drop analysis for 4 AWG conductors operating at 480V 3-Phase (three-phase). The 4 AWG copper conductor has a resistance of 0.308 ohms per 1000 feet and an ampacity of 85 amps at 75 degrees C per NEC Table 310.16. Use the tables below to determine the voltage drop at any distance and amperage combination, or to find the maximum distance you can run 4 AWG wire while staying within the NEC recommended voltage drop limits.

Wire Gauge
4 AWG
Voltage
480V 3-Phase
Cu Ampacity
85A
Cu Resistance
0.308 Ω/kft

Maximum Distance for 4 AWG at 480V 3-Phase

The table below shows the maximum one-way distance you can run 4 AWG copper conductor at 480V 3-Phase for each amperage level while maintaining voltage drop at or below 3% (branch circuit) and 5% (feeder + branch combined). If your planned run exceeds these distances, you must use a larger wire gauge. These values assume three-phase power with a 1.732 multiplier in the voltage drop formula.

Amperage Max Distance (3%) Max Distance (5%) 3% Drop = 14.4V
5A 5398 ft 8997 ft 14.4 V
10A 2699 ft 4498 ft 14.4 V
15A 1799 ft 2999 ft 14.4 V
20A 1349 ft 2249 ft 14.4 V
25A 1079 ft 1799 ft 14.4 V
30A 899 ft 1499 ft 14.4 V
40A 674 ft 1124 ft 14.4 V
50A 539 ft 899 ft 14.4 V
60A 449 ft 749 ft 14.4 V
80A 337 ft 562 ft 14.4 V
100A (exceeds ampacity) 269 ft 449 ft 14.4 V

Voltage Drop Table — 4 AWG Copper at 480V 3-Phase

Complete voltage drop matrix for 4 AWG copper conductor at 480V 3-Phase. Each cell shows the voltage drop in volts and percentage. Cells in red exceed the 3% NEC recommendation for branch circuits. Cells within the green range are NEC compliant. This table uses the three-phase voltage drop formula with a conductor resistance of 0.308 ohms per 1000 feet.

Distance 5A10A15A20A25A30A40A50A60A80A100A
25 ft 0.1V
0.0%
0.1V
0.0%
0.2V
0.0%
0.3V
0.1%
0.3V
0.1%
0.4V
0.1%
0.5V
0.1%
0.7V
0.1%
0.8V
0.2%
1.1V
0.2%
1.3V
0.3%
50 ft 0.1V
0.0%
0.3V
0.1%
0.4V
0.1%
0.5V
0.1%
0.7V
0.1%
0.8V
0.2%
1.1V
0.2%
1.3V
0.3%
1.6V
0.3%
2.1V
0.4%
2.7V
0.6%
75 ft 0.2V
0.0%
0.4V
0.1%
0.6V
0.1%
0.8V
0.2%
1.0V
0.2%
1.2V
0.3%
1.6V
0.3%
2.0V
0.4%
2.4V
0.5%
3.2V
0.7%
4.0V
0.8%
100 ft 0.3V
0.1%
0.5V
0.1%
0.8V
0.2%
1.1V
0.2%
1.3V
0.3%
1.6V
0.3%
2.1V
0.4%
2.7V
0.6%
3.2V
0.7%
4.3V
0.9%
5.3V
1.1%
125 ft 0.3V
0.1%
0.7V
0.1%
1.0V
0.2%
1.3V
0.3%
1.7V
0.3%
2.0V
0.4%
2.7V
0.6%
3.3V
0.7%
4.0V
0.8%
5.3V
1.1%
6.7V
1.4%
150 ft 0.4V
0.1%
0.8V
0.2%
1.2V
0.3%
1.6V
0.3%
2.0V
0.4%
2.4V
0.5%
3.2V
0.7%
4.0V
0.8%
4.8V
1.0%
6.4V
1.3%
8.0V
1.7%
200 ft 0.5V
0.1%
1.1V
0.2%
1.6V
0.3%
2.1V
0.4%
2.7V
0.6%
3.2V
0.7%
4.3V
0.9%
5.3V
1.1%
6.4V
1.3%
8.5V
1.8%
10.7V
2.2%
250 ft 0.7V
0.1%
1.3V
0.3%
2.0V
0.4%
2.7V
0.6%
3.3V
0.7%
4.0V
0.8%
5.3V
1.1%
6.7V
1.4%
8.0V
1.7%
10.7V
2.2%
13.3V
2.8%
300 ft 0.8V
0.2%
1.6V
0.3%
2.4V
0.5%
3.2V
0.7%
4.0V
0.8%
4.8V
1.0%
6.4V
1.3%
8.0V
1.7%
9.6V
2.0%
12.8V
2.7%
16.0V
3.3%
400 ft 1.1V
0.2%
2.1V
0.4%
3.2V
0.7%
4.3V
0.9%
5.3V
1.1%
6.4V
1.3%
8.5V
1.8%
10.7V
2.2%
12.8V
2.7%
17.1V
3.6%
21.3V
4.5%
500 ft 1.3V
0.3%
2.7V
0.6%
4.0V
0.8%
5.3V
1.1%
6.7V
1.4%
8.0V
1.7%
10.7V
2.2%
13.3V
2.8%
16.0V
3.3%
21.3V
4.5%
26.7V
5.6%

When to Use 4 AWG at 480V 3-Phase

4 AWG wire at 480V 3-Phase is appropriate for circuits where the amperage does not exceed 85 amps (copper, 75 degrees C) and the voltage drop at the planned distance stays within NEC recommendations. At short distances under 50 feet, 4 AWG handles 68-amp loads with comfortable voltage drop margin. As the distance increases, the voltage drop grows proportionally, and at some point a larger gauge becomes necessary.

If 4 AWG does not provide adequate voltage drop performance for your run distance, consider the next larger gauge. Each step up in wire size roughly doubles the maximum distance for the same voltage drop percentage. Alternatively, if the circuit operates at 120 volts and the distance is problematic, consider whether the load can be served by a 240-volt circuit instead, which halves the percentage voltage drop and doubles the effective run distance for the same wire gauge.

For aluminum conductors, 4 AWG has an ampacity of 68 amps at 75 degrees C and a resistance of 0.508 ohms per 1000 feet. The higher resistance means aluminum requires approximately 65% more distance correction compared to copper, often requiring an increase of one or two gauge sizes to match copper's voltage drop performance at the same distance.

Related Wire Sizes at 480V 3-Phase

Compare voltage drop performance across different wire gauges at 480V 3-Phase. Larger gauges have lower resistance and can run longer distances with less voltage drop.

Tools and Training for Electricians

Quality resources for your next wiring project.

Some links above are affiliate links — if you buy through them we may earn a small commission at no extra cost to you. As an Amazon Associate we earn from qualifying purchases.